Configuration Mode (ConF)
95
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
CL2
*
[I Limit. 2 value]
0 to 1.5 In (1)
1.5 In (1)
NOTICE
OVERHEATING AND DAMAGE TO THE MOTOR
•
Verify that the m otor is properly rated for the m axim um current to be applied to the m otor.
•
Cons ider the duty cycle of the m otor and all factors of your application including derating requirements in
determ ining the current lim it.
Failure to follow these instructions can result in equipment damage.
See page
218
.
Note :
If the setting is less than 0.25 In, the drive may lock in
[Output Phas e Loss]
(OPL)
fault mode if this has been enabled
(see page
256
). If it is less than the no-load motor current, the motor cannot run.
FLU
[Motor fluxing]
[No]
(FnO)
*
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
If the param eter
[Motor fluxing]
(FLU)
is s et to
[Continuous]
(FCt)
, fluxing is always active, even if the
m otor does not run.
•
Verify that us ing this s etting does not res ult in uns afe conditions.
Failure to follow these instructions will result in death or serious injury.
NOTICE
OVERHEATING AND DAMAGE TO THE MOTOR
Verify that the connected m otor is properly rated for the flux current to be applied in order to avoid overheating
and dam age to the m otor.
Failure to follow these instructions can result in equipment damage.
The paramet er is visible if
[Mot or control type]
(Ctt)
page
105
is not set to
[Sync . mot.]
(SYn)
.
In order to obtain rapid high torque on startup, magnetic flux needs to already have been established in the motor.
In
[Cont in uo us]
(FCt)
mode, the drive automatic ally builds up flux when it is powered up.
In
[Not cont.]
(FnC)
mode, fluxing occurs w hen the motor starts up.
The flux current is greater than
[Rate d m ot. current]
(nCr)
w hen the flux is established and is then adjusted to the motor
magnetizing current. See page
189
.
[Not cont.]
(FnC)
: Non-continuous mode
[Continuous ]
(FCt)
: Continuous mode. This option is not possible if
[Auto DC inje ction]
(AdC)
page
176
is
[Ye s ]
(YES)
or if
[Type of stop]
(Stt)
page
173
is
[Free w he e l]
(nSt)
.
[No]
(FnO)
: Function inactive. This option is not possible if
[Brak e as s ignm e nt]
(bLC)
page
194
is not
[No]
(nO)
.
2 s
FnC
FCt
FnO
tLS
[Low speed time out]
0 to 999.9 s
0 s
Maximum operating time at
[Low s pe e d]
(LSP)
(see page
87
).
Follow ing operation at LSP for a defined period, a motor stop is requested automatically. The motor w ill restart if the reference
is greater than LSP and if a run command is still present. See page
213
.
Note :
A value of 0 indicates an unlimited period of time.
Note:
If
[Low spee d time out]
(tLS)
is not 0,
[Type of stop]
(Stt)
page
173
is forced to
[Ra mp stop]
(rMP)
(only if a
ramp stop can be configured).
JGF
*
[Jog frequency]
0 to 10 Hz
10 Hz
Reference in jog operation. See page
178
.
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > SET-
Содержание ER24 Series
Страница 1: ...BLEMO ER24 Variable Speed Drives for Asynchronous and Synchronous Motors Programming Manual 05 2018 ...
Страница 6: ...6 Table of Contents ...
Страница 14: ...16 ...
Страница 34: ...Overview 36 ...
Страница 40: ...42 ...
Страница 74: ...Monitoring Mode MOn 76 ...
Страница 241: ......
Страница 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Страница 294: ...Interface ItF 294 ...
Страница 298: ...298 Open Save as trA ...
Страница 302: ...Multipoint Screen 302 ...
Страница 304: ...304 ...
Страница 306: ...Maintenance 306 ...
Страница 316: ...Diagnostics and Troubleshooting 316 ...
Страница 318: ...318 ...
Страница 340: ...Index of Parameter Codes 340 ...
Страница 343: ......
Страница 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...