Configuration Mode (ConF)
216
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
FUn-
[APPLICATION FUNCT.]
(continued)
tOL-
[TORQUE LIMITATION]
tLA
[Torque limit. activ.]
[No]
(nO)
nO
If the assigned input or bit is at 0, the function is inactive.
If the assigned input or bit is at 1, the function is active.
[No]
(nO)
: Function inactive
[Ye s ]
(YES)
: Function alw ays active
[LI1]
(LI1)
: Logical input LI1
[...]
(...)
: See the assignment conditions on page
153
YES
LI1
...
IntP
[Torque increment]
[1%]
(1)
*
This parameter cannot be accessed if
[Torque lim it. activ.]
(tLA)
is set to
[No]
(nO)
.
Selection of units for the
[M otoring torque lim ]
(tLIM)
and
[Ge n. torque lim ]
(tLIG)
parameters.
[0,1%]
(0.1)
: Unit 0.1%
[1%]
(1)
: Unit 1%
0.1
1
tLIM
[Motoring torque lim]
0 to 300%
100%
*
This parameter cannot be accessed if
[Torque lim it. activ.]
(tLA)
is set to
[No]
(nO)
.
Torque limitation in motor mode, as a % or in 0.1% increments of the rated torque in accordance with the
[Torque incre m e nt ]
(IntP)
paramet er.
(1)
tLIG
[Gen. torque lim]
0 to 300%
100%
*
This parameter cannot be accessed if
[Torque lim it. activ.]
(tLA)
is set to
[No]
(nO)
.
Torque limitation in generator mode, as a % or in 0.1% increments of the rated torque in accordance with the
[Torque incre m e nt ]
(IntP)
paramet er.
(1)
tAA
[Torque ref. assign.]
[No]
(nO)
nO
If the function is assigned, the limitation varies betw een 0% and 300% of the rated torque on the basis of the 0% to 100% signal
applied to the assigned input.
Examples:
12 mA on a 4-20 mA input results in limitation to 150% of the rated torque.
2.5 V on a 10 V input results in 75% of the rated torque.
[No]
(nO)
: Not assigned (function inactive)
[AI1]
(AI1)
: Analog input
[AI2]
(AI2)
: Analog input
[AI3]
(AI3)
: Analog input
[RP]
(PI)
: Pulse input
[AI Virtual 1]
(AIU1)
: Virtual analog input 1 w ith the jog dial
[AI Virtual 2]
(AIU2)
: Virtual input via communication bus, to be configured via
[AI2 ne t. channe l]
(AIC2)
page
135
.
[OA01]
(OA01)
: Function blocks: Analog Output 01
...
[OA10]
(OA10)
: Function blocks: Analog Output 10
AI1
AI2
AI3
PI
AIU1
AIU2
OA01
...
OA10
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > FUN- > TOL-
Содержание ER24 Series
Страница 1: ...BLEMO ER24 Variable Speed Drives for Asynchronous and Synchronous Motors Programming Manual 05 2018 ...
Страница 6: ...6 Table of Contents ...
Страница 14: ...16 ...
Страница 34: ...Overview 36 ...
Страница 40: ...42 ...
Страница 74: ...Monitoring Mode MOn 76 ...
Страница 241: ......
Страница 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Страница 294: ...Interface ItF 294 ...
Страница 298: ...298 Open Save as trA ...
Страница 302: ...Multipoint Screen 302 ...
Страница 304: ...304 ...
Страница 306: ...Maintenance 306 ...
Страница 316: ...Diagnostics and Troubleshooting 316 ...
Страница 318: ...318 ...
Страница 340: ...Index of Parameter Codes 340 ...
Страница 343: ......
Страница 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...