Configuration Mode (ConF)
251
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
FLt-
[FAULT MANAGEMENT]
(continued)
rSt-
[FAULT RESET]
rSF
[Fault reset]
[No]
(nO)
nO
Detected faults are cleared manually w hen the assigned input or bit changes to 1, if the cause of the detected fault has
disappeared.
The STOP/RESET key on the graphic display terminal performs the same function.
Follow ing detected faults can be cleared manually :
ASF
,
brF
,
bLF
,
CnF
,
COF
,
dLF
,
EPF1
,
EPF2
,
FbES
,
FCF2
,
InF9
,
InFA
,
InFb
,
LCF
,
LFF3
,
ObF
,
OHF
,
OLC
,
OLF
,
OPF1
,
OPF2
,
OSF
,
OtFL
,
PHF
,
PtFL
,
SCF4
,
SCF5
,
SLF1
,
SLF2
,
SLF3
,
SOF
,
SPF
,
SSF
,
tJF
,
tnF
and
ULF
.
Note :
If
[Reset restricted fault configuration]
(HrFC)
is set to
[Yes]
(YES)
, the additional follow ing detected fault can be
cleared manually:
OCF
,
SCF1
,
SCF3
. See page
252
[No]
(nO)
: Function inactive
[Ye s ]
(YES)
: Logical input LI1
[...]
(...)
: See the assignment conditions on page
153
LI1
...
rPA
[Product reset assig.]
[No]
(nO)
*
The Restart function performs a Fault Reset and then restarts the drive. During this Restart procedure, the drive goes through
the same steps as if it had been sw itched off and on again. Depending on the w iring and the configuration of the drive, this may
result in immediate and unanticipated operation. The Restart function can be assigned to a digital input.
WARNING
UNANTICIPATED EQUIPMENT OPERATION
The Res tart function perform s a Fault Res et and res tarts the drive.
•
Verify that activating this function does not res ult in uns afe conditions.
Failure to follow these instructions can result in death, serious injury, or equipment damage
This parameter can only be modified if
[3.1 ACCE S S LEVE L]
(LAC)
is set to
[Expe rt ]
(EPr)
mode.
Drive reinitialization via logic input. Can be used to reset all detected faults without having to disconnect the drive from the power
supply. The drive is reinitialized on a rising edge (change from 0 to 1) of the assigned input. The drive can only be reinitialized
w hen locked.
To assign reinitialization, press and hold dow n the ENT key for 2 s.
[No]
(nO)
: Function inactive
[LI1]
(LI1)
: Logical input LI1
...
[LI6]
(LI6)
: Logical input LI6
[LAI1]
(LAI1)
: Logical input AI1
[LAI2]
(LAI2)
: Logical input AI2
[OL01]
(OL01)
: Function blocks: Logical Output 01
...
[OL10]
(OL10)
: Function blocks: Logical Output 10
nO
LI1
...
LI6
LAI1
LAI2
OL01
...
OL10
rP
[Product reset]
[No]
(nO)
*
The Restart function performs a Fault Reset and then restarts the drive. During this Restart procedure, the drive goes through
the same steps as if it had been sw itched off and on again. Depending on the w iring and the configuration of the drive, this may
result in immediate and unanticipated operation.
WARNING
UNANTICIPATED EQUIPMENT OPERATION
The Res tart function perform s a Fault Res et and res tarts the drive.
•
Verify that activating this function does not res ult in uns afe conditions.
.
Failure to follow these instructions can result in death, serious injury, or equipment damage
This parameter can only be accessed if
[3.1 ACCESS LEVEL]
(LAC)
is set to
[Expe rt]
(EPr)
mode.
Drive reinitialization. Can be used to reset all detected faults w ithout having to disconnect the drive from the pow er supply.
[No]
(nO)
: Function inactive
[Ye s ]
(YES)
: Reinitialization. Press and hold dow n the ENT key for 2 s. The parameter changes back to
[No]
(nO)
automatically as soon as the operation is complete. The drive can only be reinitialized w hen locked.
nO
YES
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > FLT- > RST-
Содержание ER24 Series
Страница 1: ...BLEMO ER24 Variable Speed Drives for Asynchronous and Synchronous Motors Programming Manual 05 2018 ...
Страница 6: ...6 Table of Contents ...
Страница 14: ...16 ...
Страница 34: ...Overview 36 ...
Страница 40: ...42 ...
Страница 74: ...Monitoring Mode MOn 76 ...
Страница 241: ......
Страница 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Страница 294: ...Interface ItF 294 ...
Страница 298: ...298 Open Save as trA ...
Страница 302: ...Multipoint Screen 302 ...
Страница 304: ...304 ...
Страница 306: ...Maintenance 306 ...
Страница 316: ...Diagnostics and Troubleshooting 316 ...
Страница 318: ...318 ...
Страница 340: ...Index of Parameter Codes 340 ...
Страница 343: ......
Страница 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...