Configuration Mode (ConF)
144
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
I_O-
[INPUTS / OUTPUTS CFG]
(continued)
AO1-
[AO1 CONFIGURATION]
AO1
nO
OCr
OFr
OFS
OrP
trq
Stq
OrS
OPS
OPF
OPE
OPI
OPr
UOP
tHr
tHr2
tHr3
tHd
tqL
d01
tqMS
OA01
...
OA10
[AO1 assignment]
[No]
(nO)
[No]
(nO)
: Not assigned
[I m otor]
(OCr)
: Current in the motor, betw een 0 and 2 In (In = rated drive current indicated in the Installation manual and on
the drive nameplate)
[Mot or freq.]
(OFr)
: Output frequenc y, from 0 to
[Max freque nc y ]
(tFr)
[Sig. o/p frq.]
(OFS)
: Signed output frequency, between -
[Max freque n cy ]
(tFr)
and +
[Max freque nc y]
(tFr)
[Ramp out.]
(OrP)
: From 0 to
[Max freque nc y ]
(tFr)
[Mot or torq.]
(trq)
: Motor torque, between 0 and 3 times the rated motor torque
[Sign. torque]
(Stq)
: Signed motor torque, betw een -3 and +3 times the rated motor torque. The + sign corresponds to the
motor mode and the - sign to the generator mode (braking).
[sign ramp]
(OrS)
: Signed ramp output, between -
[Max freque nc y]
(tFr)
and +
[Max freque nc y ]
(tFr)
.
[PID re f.]
(OPS)
: PID regulator reference betw een
[M in PID re fe rence ]
(PIP1)
and
[M ax PID re fe rence ]
(PIP2)
.
[PID fe e dbk ]
(OPF)
: PID regulator feedback betw een
[M in PID fe e dback ]
(PIF1)
and
[M ax PID fe e dback ]
(PIF2)
[PID e rror]
(OPE)
: PID regulator error betw een- 5 % and + 5 % of (
[M ax PID fe e dback ]
(PIF2)
-
[M in PID fe e dback ]
(PIF1)
)
[PID output]
(OPI)
: PID regulator output betw een
[Low s pe e d]
(LSP)
and
[High s pe e d]
(HSP)
[Mot. powe r]
(OPr)
: Motor power, between 0 and 2.5 times
[Rate d mot or powe r]
(nPr)
[M otor volt.]
(UOP)
: Voltage applied to the motor, betw een 0 and
[Rate d m otor volt.]
(UnS)
[M ot the rm al]
(tHr)
: Motor thermal state, betw een 0 and 200% of the rated thermal state
[M ot the rm2]
(tHr2)
: Motor thermal state 2, betw een 0 and 200 % of the rated thermal state
[M ot the rm3]
(tHr3)
: Motor thermal state 3, betw een 0 and 200% of the rated thermal state
[Drv the rm al]
(tHd)
: Drive thermal state, betw een 0 and 200% of the rated thermal state
[Torque lim.]
(tqL)
: Torque limit, between 0 and 3 times the rated motor torque
[dO1]
(dO1)
: Assignment to a logic output. This assignment can only appear if
[DO1 as s ignment]
(dO1)
has been assigned.
This is the only possible choice in this case, and is only displayed for informational purposes.
[Torque 4Q]
(tqMS)
: Signed motor torque, betw een -3 and +3 times the rated motor torque. The + sign and the - sign
correspond to the physical direction of the torque, regardless of mode (motor or generator).
[OA01]
(OA01)
: Function blocks: Analog Output 01
...
[OA10]
(OA10)
: Function blocks: Analog Output 10
AO1t
10U
0A
[AO1 Type]
[Curre nt]
(0A)
[Voltage ]
(10U)
: Voltage output
[Curre nt]
(0A)
: Current output
AOL1
*
[AO1 min Output]
0 to 20.0 mA
0 mA
This parameter can be accessed if
[AO1 Type ]
(AO1t)
is set to
[Curre nt]
(0A)
.
AOH1
*
[AO1 max Output]
0 to 20.0 mA
20.0 mA
This parameter can be accessed if
[AO1 Type ]
(AO1t)
is set to
[Curre nt]
(0A)
.
UOL1
*
[AO1 min Output]
0 to 10.0 V
0 V
This parameter can be accessed if
[AO1 Type ]
(AO1t)
is set to
[Voltage ]
(10U)
.
UOH1
*
[AO1 max Output]
0 to 10.0 V
10.0 V
This parameter can be accessed if
[AO1 Type ]
(AO1t)
is set to
[Voltage ]
(10U)
.
ASL1
[Scaling AO1 min]
0 to 100.0%
0%
Scaling of the low er limit of the assigned parameter, as a % of the maximum possible variation.
ASH1
[Scaling AO1 max]
0 to 100.0%
100.0%
Scaling of the upper limit of the assigned parameter, as a % of the maximum possible variation.
AO1F
[AO1 Filter]
0 to 10.00 s
0 s
Interference filtering. This parameter is forced to 0 if
[AO1 as s ignment]
(AO1)
is set to
[dO1]
(dO1)
.
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from w ithin the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
*
Содержание ER24 Series
Страница 1: ...BLEMO ER24 Variable Speed Drives for Asynchronous and Synchronous Motors Programming Manual 05 2018 ...
Страница 6: ...6 Table of Contents ...
Страница 14: ...16 ...
Страница 34: ...Overview 36 ...
Страница 40: ...42 ...
Страница 74: ...Monitoring Mode MOn 76 ...
Страница 241: ......
Страница 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Страница 294: ...Interface ItF 294 ...
Страница 298: ...298 Open Save as trA ...
Страница 302: ...Multipoint Screen 302 ...
Страница 304: ...304 ...
Страница 306: ...Maintenance 306 ...
Страница 316: ...Diagnostics and Troubleshooting 316 ...
Страница 318: ...318 ...
Страница 340: ...Index of Parameter Codes 340 ...
Страница 343: ......
Страница 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...