Configuration Mode (ConF)
118
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
drC-
[MOTOR CONTROL]
(continued)
SPG
*
[Speed prop. gain]
0 to 1,000%
40%
Speed loop proportional gain.
Visible if
[Mot or control type]
(Ctt)
is not set to
[Standa rd]
(Std)
,
[V/F 5pts]
(UFS)
or
[V/F Qua d.]
(UFq)
.
SPGU
*
[UF inertia comp.]
0 to 1,000%
40%
Inertia factor for following motor control law s.
Visible if
[Mot or control type]
(Ctt)
is set to
[Standa rd]
(Std)
,
[V/F 5pts]
(UFS)
or
[V/F Qua d.]
(UFq)
.
SIt
*
[Speed time integral]
1 to 65,535 ms
63 ms
Speed loop integral time constant.
Visible if
[Mot or control type]
(Ctt)
is not set to
[Standa rd]
(Std)
,
[V/F 5pts]
(UFS)
or
[V/F Qua d.]
(UFq)
.
SFC
*
[K speed loop filter]
0 to 100
65
Speed filter coefficient (0(IP) to 100(PI)).
FFH
*
[Spd est. filter time]
0 to 100 ms
6.4 ms
Accessible in Expert mode only.
Frequency to filter the estimated speed.
CrtF
*
[Cur. ref. filter time]
0 to 100 ms
3.2 ms
Accessible in Expert mode only.
Filter time of the current reference filter [of control law (if
[No]
(nO)
: stator natural frequency)].
UFr
[IR compensation]
0 to 200%
100%
Used to optimize torque at very low speed, or to adapt to special cases (for example: for motors connected in parallel, decrease
[IR compe ns a tio n]
(UFr)
). If there is insufficient torque at low speed, increase
[IR compe ns at io n]
(UFr)
. A too high value
can avoid the motor to start (locking) or change the current limiting mode.
SLP
*
[Slip compensation]
0 to 300%
100%
This parameter cannot be accessed if
[Mot or contro l type]
(Ctt)
is set to
[Sync . mot.]
(SYn)
.
This parameter is written at 0% when
[Mot or control type]
(Ctt)
is set to
[V/F Qua d.]
(UFq)
.
Adjusts the slip compensation around the value set by the rated motor speed.
The speeds given on motor nameplates are not necessarily exact.
If slip setting is low er than actual slip: The motor is not rotating at the correct speed in steady state, but at a speed low er than
the reference.
If slip setting is higher than actual slip: The motor is overcompensated and the speed is unstable.
U1
*
[U1]
0 to 800 V according to rating 0 V
V/F profile setting.
This parameter can be accessed if
[Mot or contro l type]
(Ctt)
is set to
[V/F 5pts]
(UF5)
.
F1
*
[F1]
0 to 599 Hz
0 Hz
V/F profile setting.
This parameter can be accessed if
[Mot or contro l type]
(Ctt)
is set to
[V/F 5pts]
(UF5)
.
U2
*
[U2]
0 to 800 V according to rating 0 V
V/F profile setting.
This parameter can be accessed if
[Mot or contro l type]
(Ctt)
is set to
[V/F 5pts]
(UF5)
.
F2
*
[F2]
0 to 599 Hz
0 Hz
V/F profile setting.
This parameter can be accessed if
[Mot or contro l type]
(Ctt)
is set to
[V/F 5pts]
(UF5)
.
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > DRC-
Содержание ER24 Series
Страница 1: ...BLEMO ER24 Variable Speed Drives for Asynchronous and Synchronous Motors Programming Manual 05 2018 ...
Страница 6: ...6 Table of Contents ...
Страница 14: ...16 ...
Страница 34: ...Overview 36 ...
Страница 40: ...42 ...
Страница 74: ...Monitoring Mode MOn 76 ...
Страница 241: ......
Страница 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Страница 294: ...Interface ItF 294 ...
Страница 298: ...298 Open Save as trA ...
Страница 302: ...Multipoint Screen 302 ...
Страница 304: ...304 ...
Страница 306: ...Maintenance 306 ...
Страница 316: ...Diagnostics and Troubleshooting 316 ...
Страница 318: ...318 ...
Страница 340: ...Index of Parameter Codes 340 ...
Страница 343: ......
Страница 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...