Configuration Mode (ConF)
112
NOTICE
OVERHEATING AND DAMAGE TO THE MOTOR
Verify that the motor is properly rated for the maximum current to be applied to the motor.
Consider the duty cycle of the motor and all factors of your application including derating requirements in
determining the current limit.
Failure to follow these instructions can result in equipment damage.
Synchronous motor parameters
Thes e param eters can be acces s ed if
[Motor control type]
(Ctt)
page
105
is s et to
[Sync. mot.]
(SYn)
.
In this cas e, the as ynchronous m otor param eters cannot be acces s ed.
Once the drive is chos en:
1- Enter the motor nameplate.
2 - Perform the tune.
•
Do an
[Auto tuning]
(tUn)
•
Check the s tate of the s ynchronous m otor s aliency (See page
113
.)
If
[Saliency m ot. s tate]
(SMOt)
dis plays
[Med s alient]
(MLS)
or
[High s alient]
(HLS)
- follow the procedure below "
3 - Improve the tune result
"
and
- follow the the procedure below "
4 - Adjust PHS
"
Or if
[Saliency m ot. s tate]
(SMOt)
dis plays
[Low s alient]
(LLS)
- follow the the procedure below "
4 - Adjust PHS
"
3 - Improve the tune results.
•
Set
[PSI align curr. m ax]
(MCr)
conform ing to the m axim um m otor current. The m axim um value of
[PSI
align curr. m ax]
(MCr)
) is lim ited by
[Current Lim itation]
(CLI)
. Without inform ation s et
[PSI align curr.
m ax]
(MCr)
to
[Auto]
(AUtO)
(s ee page
116
)
•
Do a s econd
(tUn)
after the
(MCr)
m odification.
4 - Adjust PHS.
Adjus t
[Syn. EMF cons tant]
(PHS)
to have optim al behavior (See page
116
.)
•
Start the m otor at m inim al s table frequency available on the m achine (without load).
•
Check and note the
[% error EMF s ync]
(rdAE)
value. (See page
117
)
- If the
[% error EMF s ync]
(rdAE)
value is lower than 0%, then
[Syn. EMF cons tant]
(PHS)
m ay be
increas ed.
- If the
[% error EMF s ync]
(rdAE)
value is upper than 0%, then
[Syn. EMF cons tant]
(PHS)
m ay
be reduced.
[% error EMF s ync]
(rdAE)
value s hould be clos ed to 0%.
•
Stop the m otor for m odify
PHS
in accordance with the value of the
rdAE
(previous ly noted).
Advices:
The drive m us t be chos en to have enough current according to the need of behavior, but not too m uch, to have
enough accuracy in the current m eas urement, es pecially with the high frequency s ignal injection (s ee
[HF inj. activation]
(HFI)
page
116
).
Perform ances m ay be higher on high s aliency m otors by activating high frequency injection function (s ee
[HF inj. activation]
(HFI)
page
116
).
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > DRC- > SYN-
Содержание ER24 Series
Страница 1: ...BLEMO ER24 Variable Speed Drives for Asynchronous and Synchronous Motors Programming Manual 05 2018 ...
Страница 6: ...6 Table of Contents ...
Страница 14: ...16 ...
Страница 34: ...Overview 36 ...
Страница 40: ...42 ...
Страница 74: ...Monitoring Mode MOn 76 ...
Страница 241: ......
Страница 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Страница 294: ...Interface ItF 294 ...
Страница 298: ...298 Open Save as trA ...
Страница 302: ...Multipoint Screen 302 ...
Страница 304: ...304 ...
Страница 306: ...Maintenance 306 ...
Страница 316: ...Diagnostics and Troubleshooting 316 ...
Страница 318: ...318 ...
Страница 340: ...Index of Parameter Codes 340 ...
Страница 343: ......
Страница 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...