Configuration Mode (ConF)
270
Process underload detected fault
A proces s underload is detected when the next event occurs and rem ains pending for a m inim um tim e
[Unld T. Del. Detect]
(ULt)
, which is configurable:
•
The m otor is in s teady s tate and the torque is below the s et underload limit (
[Unld. Thr. 0. Speed.]
(
LUL
)
,
[Unld. Thr. Nom. Speed.]
(
LUn
)
,
[Unld. Freq. Thr. Det.]
(
rMUd
)
param eters ).
•
The m otor is in s teady s tate when the offs et between the frequency reference and m otor frequency falls
below the configurable thres hold
[Hysteresis Freq. Att.]
(Srb)
.
Torque as a % of
the rated torque
Betw een zero frequency and the rated frequency,
the curve reflects the follow ing equation:
torque =
LUL
+
(
LUn
-
LUL
) x (frequency)
2
(rated frequency)
2
The underload function is not active for
frequencies below
[Unld. Freq. Thr. Det.]
(
rMUd
)
.
A relay or a logic output can be as s igned to the s ignaling of this detected fault in the
[INPUTS / OUTPUTS CFG]
(I_O-)
m enu.
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
FLt-
[FAULT MANAGEMENT]
(continued)
ULd-
[PROCESS UNDERLOAD]
ULt
[Unld T. Del. Detect.]
0 to 100 s
0 s
Underload detection time delay.
A value of 0 deactivates the function and makes the other parameters inaccessible.
LUn
*
[Unld. Thr. Nom. Speed.]
20 to 100%
60%
Underload threshold at rated motor frequency (
[Rate d m otor freq.]
(FrS)
page
86
), as a % of the rated motor torque.
LUL
*
[Unld. Thr. 0. Speed.]
0 to
[Unld.Thr.Nom.Speed]
(LUn)
0%
Underload threshold at zero frequency, as a % of the rated motor torque.
rMUd
*
[Unld. Freq. Thr. Det.]
0 to 599 Hz
0 Hz
Minimum frequency underload detection threshold.
Srb
*
[Hysteresis Freq. Att.]
0.3 to 599 Hz
0.3 Hz
Maximum deviation betw een the frequency reference and the motor frequency, which defines steady state operation.
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > FLT - > ULD-
zone
0
Содержание ER24 Series
Страница 1: ...BLEMO ER24 Variable Speed Drives for Asynchronous and Synchronous Motors Programming Manual 05 2018 ...
Страница 6: ...6 Table of Contents ...
Страница 14: ...16 ...
Страница 34: ...Overview 36 ...
Страница 40: ...42 ...
Страница 74: ...Monitoring Mode MOn 76 ...
Страница 241: ......
Страница 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Страница 294: ...Interface ItF 294 ...
Страница 298: ...298 Open Save as trA ...
Страница 302: ...Multipoint Screen 302 ...
Страница 304: ...304 ...
Страница 306: ...Maintenance 306 ...
Страница 316: ...Diagnostics and Troubleshooting 316 ...
Страница 318: ...318 ...
Страница 340: ...Index of Parameter Codes 340 ...
Страница 343: ......
Страница 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...