Configuration Mode (ConF)
256
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
FLt-
[FAULT MANAGEMENT]
(continued)
OPL-
[OUTPUT PHASE LOSS]
OPL
[Output Phase Loss]
[Ye s ]
(YES)
2 s
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
If output phas e monitoring is disabled, phase loss and, by im plication, accidental disconnection of cables, are
not detected.
•
Verify that the s etting of this param eter does not res ult in uns afe conditions.
Failure to follow these instructions will result in death or serious injury.
Note:
[Out put phas e loss]
(OPL)
is set to
[No]
(nO)
when
[Mot or control type]
(Ctt)
page
105
is set to
[Sync. mot .]
(SYn)
. For other
[Motor contro l type]
(Ctt)
configurations,
[Out put phase loss]
(OPL)
is forced to
[Yes]
(YES)
if brake logic control is configured.
[No]
(nO)
: Function inactive
[Ye s ]
(YES)
: Tripping on
[Output phas e los s ]
(OPL)
w ith freew heel stop
[Output cut]
(OAC)
: No fault triggered, but management of the output voltage in order to avoid an overcurrent when the link
w ith the motor is re-established and catch on the fly performed (even if this function has not been configured).
The drive sw itches to
[Output cut]
(SOC)
state after
[OutPh time de tect]
(Odt)
time. Catch on fly is possible as soon as the
drive is in Stand by output cut
[Output cut]
(SOC)
state.
nO
YES
OAC
Odt
[OutPh time detect]
0.5 to 10 s
0.5 s
Time delay for taking the
[Output Phas e Loss]
(OPL)
detected fault into account.
FLt-
[FAULT MANAGEMENT]
(continued)
IPL-
[INPUT PHASE LOSS]
IPL
[Input phase loss]
According to drive rating
*
Cannot be accessed if drive rating is ATV
ppp
M2.
In this case, no factory settings value.
Factory setting :
[Fre ewheel]
(YES)
for drive rating ER24
ppp
N4
p
.
If 1 phase disappears and if this leads to performance decrease, the drive switches to fault mode
[Input phas e loss]
(PHF)
.
If 2 or 3 phases disappear, the drive trips in
[Input phase loss]
(PHF)
.
[Ignore]
(nO)
: Detected fault ignored
[Fre ewheel]
(YES)
: Detected fault w ith freewheel stop
2 s
nO
YES
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > OPL-/IPL-
Содержание ER24 Series
Страница 1: ...BLEMO ER24 Variable Speed Drives for Asynchronous and Synchronous Motors Programming Manual 05 2018 ...
Страница 6: ...6 Table of Contents ...
Страница 14: ...16 ...
Страница 34: ...Overview 36 ...
Страница 40: ...42 ...
Страница 74: ...Monitoring Mode MOn 76 ...
Страница 241: ......
Страница 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Страница 294: ...Interface ItF 294 ...
Страница 298: ...298 Open Save as trA ...
Страница 302: ...Multipoint Screen 302 ...
Страница 304: ...304 ...
Страница 306: ...Maintenance 306 ...
Страница 316: ...Diagnostics and Troubleshooting 316 ...
Страница 318: ...318 ...
Страница 340: ...Index of Parameter Codes 340 ...
Страница 343: ......
Страница 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...