Configuration Mode (ConF)
171
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
tA2
[End Acc round]
0 to 100%
10%
*
Rounding of end of acceleration ramp as a % of the
[Acce le ration]
(ACC)
or
[Acce le ration 2]
(AC2)
ramp time.
Can be set betw een 0 and (100% -
[Be gin Acc round]
(tA1)
).
This parameter can be accessed if the
[Ramp type]
(rPt)
is
[Cust o m ize d]
(CUS)
.
(1)
tA3
[Begin Dec round]
0 to 100%
10%
*
Rounding of start of deceleration ramp as a % of the
[De ce le ration]
(dEC)
or
[De ce le ration 2]
(dE2)
ramp time.
Can be set betw een 0 and 100%.
This parameter can be accessed if the
[Ramp type]
(rPt)
is
[Cust o m ize d]
(CUS)
.
(1)
tA4
[End Dec round]
0 to 100%
10%
*
Rounding of end of deceleration ramp as a % of the
[De ce le ration]
(dEC)
or
[De ce le ration 2]
(dE2)
ramp time.
Can be set betw een 0 and (100% -
[Be gin De c round]
(tA3)
).
This parameter can be accessed if the
[Ramp type]
(rPt)
is
[Cust o m ize d]
(CUS)
.
(1)
Frt
[Ramp 2 threshold]
0 to 599 Hz according to rating 0 Hz
Ramp sw itching threshold
The 2nd ramp is switched if the value of
[Ramp 2 thres ho ld]
(Frt)
is not 0 (0 deactivates the function) and the output
frequency is greater than
[Ramp 2 thres hold]
(Frt)
.
Threshold ramp sw itching can be combined w ith
[Ram p switch as s.]
(rPS)
sw itching as follows:
rPS
[Ramp switch ass.]
[No]
(nO)
Identical to
[Re f.1B channe l]
(Fr1b)
page
167
.
AC2
[Acceleration 2]
0.00 to 6,000 s (2)
5.0 s
*
Time to accelerate from 0 to the
[Rate d m otor freq.]
(FrS)
. To have repeatability in ramps, the value of this parameter must
be set according to the possibility of the application.
This parameter can be accessed if
[Ramp 2 thres hold]
(Frt)
is greater than 0 or if
[Ra mp switc h ass.]
(rPS)
is assigned.
(1)
dE2
[Deceleration 2]
0.00 to 6,000 s (2)
5.0 s
*
Time to decelerate from
[Rate d m otor freq.]
(FrS)
to 0. To have repeatability in ramps, the value of this parameter must be
set according to the possibility of the application.
This parameter can be accessed if
[Ramp 2 thres hold]
(Frt)
is greater than 0 or if
[Ra mp switc h ass.]
(rPS)
is assigned.
(1)
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > FUN- > RPT-
LI or bit
Fre que ncy
Ram p
0
< Frt
ACC, dEC
0
> Frt
AC2, dE2
1
< Frt
AC2, dE2
1
> Frt
AC2, dE2
Содержание ER24 Series
Страница 1: ...BLEMO ER24 Variable Speed Drives for Asynchronous and Synchronous Motors Programming Manual 05 2018 ...
Страница 6: ...6 Table of Contents ...
Страница 14: ...16 ...
Страница 34: ...Overview 36 ...
Страница 40: ...42 ...
Страница 74: ...Monitoring Mode MOn 76 ...
Страница 241: ......
Страница 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Страница 294: ...Interface ItF 294 ...
Страница 298: ...298 Open Save as trA ...
Страница 302: ...Multipoint Screen 302 ...
Страница 304: ...304 ...
Страница 306: ...Maintenance 306 ...
Страница 316: ...Diagnostics and Troubleshooting 316 ...
Страница 318: ...318 ...
Страница 340: ...Index of Parameter Codes 340 ...
Страница 343: ......
Страница 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...