Diagnostics and Troubleshooting
314
Fault detection codes that are cleared as soon as their cause disappears
De te cte d Fault Nam e
Probable cause
Re m e dy
CFF
[Incorrect config.]
•
Option card changed or removed.
•
Control block replaced by a control block
configured on a drive w ith a different
rating.
•
The current configuration is inconsistent.
•
Check that there are no card errors.
•
In the event of the option card being changed/removed
deliberately, see the remarks below .
•
Check that there are no card errors.
•
In the event of the control block being changed
deliberately, see the remarks below .
•
Return to factory settings or retrieve the backup
configuration, if it is valid (see page
81
).
CFI
[Invalid config.]
•
Invalid configuration.
The configuration loaded in the drive via
the bus or communication netw ork is
inconsistent.
•
Check the configuration loaded previously.
•
Load a compatible configuration.
CFI2
CSF
[Ch. Sw . fault]
•
Sw itch to not valid channels
.
•
Check the function parameters.
dLF
[Dynam ic load fault]
•
Abnormal load variation.
•
Check that the load is not blocked by an obstacle.
•
Removal of a run command causes a reset.
FbE
[FB fault]
•
Function blocks error.
•
See
[FB Fault]
(FbFt)
for more details.
HCF
[Cards pairing]
•
The
[CARDS PAIRING]
(PPI-)
function page
269
has been configured
and a drive card has been changed.
•
In the event of a card error, reinsert the original card.
•
Confirm the configuration by entering the
[Pairin g pass w ord]
(PPI)
if the card was changed
deliberately.
PHF
[Input phase los s]
•
Drive incorrectly supplied or a fuse
blow n.
•
One phase missing.
•
3-phase ER24 used on a single-phase
supply mains.
•
Unbalanced load.
This protection only operates w ith the drive
on load.
•
Check the pow er connection and the fuses.
•
Use a 3-phase supply mains.
•
Disable the detected fault by
[Input phas e loss ]
(IPL)
=
[No]
(nO)
page
86
.
USF
[Unde rvoltage]
•
Supply mains too low .
•
Transient voltage dip.
•
Check the voltage and the parameters of
[UNDERV OLTA G E M GT]
(USb-)
, page
259
.
Option card changed or removed
When an option card is rem oved or replaced by another, the drive locks in
[Incorrect config.]
(CFF)
fault
m ode on power-up. If the card has been deliberately changed or rem oved, the detected fault can be cleared
by pres s ing the ENT key twice, which caus es the factory s ettings to be res tored (s ee page
81
) for the
param eter groups affected by the card. Thes e are as follows :
Card replaced by a card of the same type
•
Com m unication cards : only the param eters that are s pecific to com m unication cards
Control block changed
When a control block is replaced by a control block configured on a drive with a different rating, the drive locks
in
[Incorrect config.]
(CFF)
fault m ode on power-up. If the control block has been deliberately changed, the
detected fault can be cleared by pres s ing the ENT key twice, which
causes all the factory settings to be
restored.
Содержание ER24 Series
Страница 1: ...BLEMO ER24 Variable Speed Drives for Asynchronous and Synchronous Motors Programming Manual 05 2018 ...
Страница 6: ...6 Table of Contents ...
Страница 14: ...16 ...
Страница 34: ...Overview 36 ...
Страница 40: ...42 ...
Страница 74: ...Monitoring Mode MOn 76 ...
Страница 241: ......
Страница 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Страница 294: ...Interface ItF 294 ...
Страница 298: ...298 Open Save as trA ...
Страница 302: ...Multipoint Screen 302 ...
Страница 304: ...304 ...
Страница 306: ...Maintenance 306 ...
Страница 316: ...Diagnostics and Troubleshooting 316 ...
Страница 318: ...318 ...
Страница 340: ...Index of Parameter Codes 340 ...
Страница 343: ......
Страница 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...