Configuration Mode (ConF)
158
Function Block Management
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
FULL
[FULL]
(continued)
FbM-
[FUNCTION BLOCKS]
MFb-
[MONIT. FUN. BLOCKS]
Note :
This section show s only w hat is possible to do w ith local or remote display on the drive. For advanced configuration using
PC software, please refer to the dedicated Function blocks manual.
FbSt
IdLE
CHEC
StOP
InIt
rUn
Err
[FB Status]
[Idle ]
(IdLE)
: No binary file in the target, the FB is w aiting for a dow nload
[Che ck prog.]
(CHEC)
: Check the program dow nloaded
[Stop]
(StOP)
: The Function blocks application is stopped
[Init]
(InIt)
: Check coherency between Logic program and Function blocks paramet ers
[Run]
(rUn)
: The Function blocks application is running
[Error]
(Err)
: An internal error has been detected. The Function blocks application is in fault state mode.
FbFt
nO
Int
bIn
InP
PAr
CAL
tOAU
tOPP
AdL
In
[FB Fault]
[No]
(nO)
: No detected fault
[Interna l]
(Int)
: Internal detected error
[Binary file ]
(bIn)
: Binary file corrupted
[Inte rn Para.]
(InP)
: Internal parameter detected error
[Para. RW]
(PAr)
: Parameter access detected error
[Calculation]
(CAL)
: Calculation detected error
[TO AUX]
(tOAU)
: TimeOut AUX task
[TO s ynch]
(tOPP)
: TimeOut in PRE/POST task
[Bad ADLC]
(AdL)
: ADLC w ith bad parameter
[Input assig.]
(In)
: Input not configured
FbI-
[FB IDENTIFICATION]
bUEr
*
[Program version]
0 to 255
-
Program user version.
bnS
*
[Program size]
0 to 65,535
-
Program file size.
bnU
[Prg. format version]
0 to 255
-
Binary format version of the drive.
CtU
[Catalog version]
0 to 65,535
-
Catalog version of the drive.
FbM-
[FUNCTION BLOCKS]
(continued)
FbCd
StOP
Strt
[FB Command]
Allow s to start and stop the function blocks manually.
[FB Com m and]
(FbCd)
is forced to
[Stop]
(StOP)
if there is no valid function blocks application in the drive memory.
[FB Comm a nd]
(FbCd)
is set to
[Start]
(Strt)
when the function blocks application switch to Run according to
[FB s tart m ode ]
(FbrM)
configuration.
Note :
As soon as the function blocks are started, the drive is considered as in running state and the modification of configuration
parameters is no longer possible.
[Stop]
(StOP)
: Function blocks application Stop command
[Start]
(Strt)
: Function blocks application Start command
Parameters described in this page can be accessed by:
DRI- > CONF > FULL > FBM- > MFB-
Содержание ER24 Series
Страница 1: ...BLEMO ER24 Variable Speed Drives for Asynchronous and Synchronous Motors Programming Manual 05 2018 ...
Страница 6: ...6 Table of Contents ...
Страница 14: ...16 ...
Страница 34: ...Overview 36 ...
Страница 40: ...42 ...
Страница 74: ...Monitoring Mode MOn 76 ...
Страница 241: ......
Страница 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Страница 294: ...Interface ItF 294 ...
Страница 298: ...298 Open Save as trA ...
Страница 302: ...Multipoint Screen 302 ...
Страница 304: ...304 ...
Страница 306: ...Maintenance 306 ...
Страница 316: ...Diagnostics and Troubleshooting 316 ...
Страница 318: ...318 ...
Страница 340: ...Index of Parameter Codes 340 ...
Страница 343: ......
Страница 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...