Configuration Mode (ConF)
213
Code
Nam e / De s cription
Adjus tment range
Factory s e tting
PIM
*
nO
AI1
AI2
AI3
PI
AIU1
OA01
...
OA10
[Manual reference]
[No]
(nO)
Manual speed input. This parameter can be accessed if
[Auto/Manual as sign.]
(PAU)
is not set to
[No]
(nO)
.
The preset speeds are active on the manual reference if they have been configured.
[No]
(nO)
: Not assigned
[Al1]
(A11)
: Analog input A1
[Al2]
(A12)
: Analog input A2
[Al3]
(A13)
: Analog input A3
[RP]
(PI)
: Pulse input
[AI virtual 1]
(AIU1)
: Virtual analog input 1 w ith the jog dial
[OA01]
(OA01)
: Function blocks: Analog Output 01
...
[OA10]
(OA10)
: Function blocks: Analog Output 10
tLS
(1)
[Low speed time out]
0 to 999.9 s
0 s
Maximum operating time at
[Low s pe e d]
(LSP)
(see
[Low s pe e d]
(LSP)
page
87
).
Follow ing operation at
[Low s peed]
(LSP)
for a defined period, a motor stop is requested automatically. The motor w ill restart
if the reference is greater than
[Low s peed]
(LSP)
and if a run command is still present.
Note :
A value of 0 indicates an unlimited period of time.
If
[Low speed time out]
(tLS)
is not 0,
[Type of stop]
(Stt)
page
173
is forced to
[Ramp stop]
(rMP)
(only if a ramp stop
can be configured).
rSL
*
2 s
[PID wake up thresh.]
0.0 to 100.0
0
WARNING
UNANTICIPATED EQUIPMENT OPERATION
Verify that activating this function does not res ult in uns afe conditions.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
If the "PID" and "Low speed operating time"
[Low s peed time out]
(tLS)
functions are configured at the same time, the PID
regulator may attempt to set a speed low er than
[Low s peed]
(LSP)
.
This results in unsatisfactory operation, w hich consists of starting, operating at low speed then stopping, and so on…
Parameter
[PID w ak e up thre s h.]
(rSL)
(restart error threshold) can be used to set a minimum PID error threshold for
restarting after a stop at prolonged
[Low s pe ed]
(LSP)
.
[PID w ak e up thresh.]
(rSL)
is a percentage of the PID error (value
depends on
[M in PID fe e dback ]
(PIF1)
and
[M ax PID fe e dback ]
(PIF2)
, see
[M in PID fe e dback ]
(PIF1)
page
210
).
The function is inactive if
[Low s pe ed time out]
(tLS)
= 0 or if
[PID w ak e up thres h.]
(rSL)
= 0.
(1) The parameter can also be accessed in the
[SETTINGS]
(SEt-)
menu.
(2) If a graphic display terminal is not in use, values greater than 9,999 w ill be displayed on the 4-digit display w ith a period
mark after the thousand digit, for example, 15.65 for 15,650.
(3) Range 0.01 to 99.99 s or 0.1 to 999.9 s or 1 to 6,000 s according to
[Ra mp incre m e nt ]
(Inr)
page
170
.
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from w ithin the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
Parameter that can be modified during operation or w hen stopped.
To change the assignment of this parameter, press the ENT key for 2 s.
2 s
*
Содержание ER24 Series
Страница 1: ...BLEMO ER24 Variable Speed Drives for Asynchronous and Synchronous Motors Programming Manual 05 2018 ...
Страница 6: ...6 Table of Contents ...
Страница 14: ...16 ...
Страница 34: ...Overview 36 ...
Страница 40: ...42 ...
Страница 74: ...Monitoring Mode MOn 76 ...
Страница 241: ......
Страница 278: ...Configuration Mode ConF 278 Access Level See Access Level LAC page 280 ...
Страница 294: ...Interface ItF 294 ...
Страница 298: ...298 Open Save as trA ...
Страница 302: ...Multipoint Screen 302 ...
Страница 304: ...304 ...
Страница 306: ...Maintenance 306 ...
Страница 316: ...Diagnostics and Troubleshooting 316 ...
Страница 318: ...318 ...
Страница 340: ...Index of Parameter Codes 340 ...
Страница 343: ......
Страница 344: ...Index of Parameter Codes 342 ER24_Programming_Manual_EN_01 2017 ...