P
Parameter
number
Parameter
Description
Factory set
ting
5890
R
Relay output QX1
None
Circulating pump Q4 : DHW circulating pump.
El imm heater HW K6
Collector pump Q5 : Circulating pump for the panels circuit.
Cons circuit pump VK1 Q15 : The VK1 consumer circuit pump can be
used for an additional consumer boiler.
Boiler pump Q1 : The pump connected is used for circulating the boil
er water.
Bypass pump Q12
Alarm output K10: Presence of an error signalled by relay. Closure of
the contact is on a time delay of 2 min.
2nd pump speed CH1 Q21
2nd pump speed CH2 Q22
2nd pump speed CH3 Q23
heating pump CH3 Q20 : The heating circuit with CC3 pump is activa
ted. (Zone V3V)
Cons circuit pump VK2 Q18
System pump Q14 : The pump connected is used as the mains
pump.
Heat gen shutoff valve Y4
Solid fuel boiler pump Q10 : Integration of a solid fuel boiler: Circ.
pump in the boiler circuit.
Time setting 5 K13 : The relay is controlled according to the settings
on timer program 5.
Buffer return valve Y15
Solar pump ext exch K9
Solar ctrl elem buffer K8
Solar ctrl elem swi pool K18 : Contact for heating the swimming pool
with solar energy (if using several heat exchangers).
Cons circuit pump VK2 Q18
Cascade pump Q25 : Boiler pump common to all boilers in a cas
cade.
St tank transfer pump Q11
Hot water mixing pump Q35
HW interm circ pump Q33
Heat request K27
Refrigeration request K28 : Cooling requirement for cooling circuit 1.
heating pump CH1 Q2 : The heating circuit with CC1 pump is activa
ted.
heating pump CH2 Q6 : The heating circuit with CC2 pump is activa
ted.
Hot water ctrl elem Q3 : Pump / distribution valve for hot water tank.
Instant WH ctrl elem Q34Pump / distribution valve for boiler producing
instantaneous hot water.
Water refill K34 : Solenoid filling valve command.
2nd boiler pump speed Q27 : 2nd boiler pump speed.
Status output K35
Status information K36
Flue gas damper K37
Fan shutdown K38 : Fan shut-down function for cutting the power to
the latter if it is not used.
heating
pump CH1
Q2
9 Settings
7609474 - v02 - 04092014
79