![Baxi POWER HT+ 1.110 Скачать руководство пользователя страница 49](http://html.mh-extra.com/html/baxi/power-ht-1-110/power-ht-1-110_installation-and-service-manual_2711894049.webp)
Neutral operating conditions.
Tab.18 Specifications of the power cable and the power source
Cable cross section (mm²)
3 x 1.5
C DJ curve (circuit breaker)
10 A
66.6.3 Accessing the terminal blocks
1. Remove the front panels.
See
Accessing the internal boiler components, page 37.
6.6.4 Wiring the terminal blocks
Use a flat-bladed screwdriver less than 3.5 mm in width.
1. Press down the spring on the terminal block with a suitable screw
driver.
2. Insert the stripped part of the wire into the corresponding connector.
Caution
The length to be stripped must be between 10 and 12 mm.
Fig.54 Pressing down the spring
MW-3000037
1
Fig.55 Connecting the wire
MW-3000038
2
6 Installation
7609474 - v02 - 04092014