Copyright 2020 Baker Hughes Company. All rights reserved.
Page 238 of 277
Table 63: Trigger Actions (full list) (cont'd.)
Action (User Level)
Color Scheme (background)
Description
Go to Run Mode 3
(Advanced)
Dark Green
The trigger will cause the motor
control to transition to Run Mode
3.
Clear LockOut
(Advanced)
Dark Green
The trigger will clear any lockout
and allow the motor control to
begin counting down for a restart
(if any trigger have any restarts
remaining).
Save 100ms Trace
(Advanced)
Dark Green
The trigger will activate the
100ms trace function. This
function saves all channels
defined on the Trace Channels
screen at 100 ms intervals from
approximately 3 minutes before
the trigger enters the set state to
3 minutes after the trigger enters
the set state.
Latched Logic
(Advanced)
Brown
The trigger when set will stay set
until a
“Clear Latches” trigger is
set. Note that the Latched Logic
trigger has no effect on the motor
control
– but can be very used as
an input when creating derived
trigger.
Clear Latches
(Advanced)
Dark Green
The trigger when set will clear all
“Latched Logic” triggers. Note
that the Clear Latches trigger has
no effect on the motor control.
Содержание Apollo 3
Страница 1: ...Copyright 2020 Baker Hughes Company All rights reserved Page 1 of 277...
Страница 46: ...Copyright 2020 Baker Hughes Company All rights reserved Page 46 of 277 Figure 20 Backspin Probes Drawing 2...
Страница 139: ...Copyright 2020 Baker Hughes Company All rights reserved Page 139 of 277 Figure 116 Murphy Switch Trigger Example 1...
Страница 266: ...Copyright 2020 Baker Hughes Company All rights reserved Page 266 of 277 Figure 227 USB Menu...
Страница 267: ......
Страница 276: ......
Страница 277: ...Index 129112 28 197705 28 197349 28 800638 28 197350 28 810280 28 197351 29...