Copyright 2020 Baker Hughes Company. All rights reserved.
Page 121 of 277
Figure 94: Downhole Limits Screen
Table 29: Download Limits Common Installations
Parameter
Default
Description
Motor Temp High
Not in Use
The motor temperature high
trigger is a Stop->Fault trigger
used to protect the motor. Select
Motor Temp High to set the limit.
Set the Trip Delay and Restart
parameters as desired.
Intake Temp High
Not In Use
The intake temperature high
trigger is a Stop->Fault trigger
used to protect the motor. Select
Intake Temp High to set the limit.
Set the Trip Delay and Restart
parameters as desired