Table 22: Parameters (cont'd.)
Parameter
Default
Description
I-Limit
2000 Amps
Maximum current output allowed
by the drive. When the drive
exceeds the specified I-Limit, the
drive frequency will be slowed to
reduce the output current. The
I-Limit function will not slow the
drive to less than Min Frequency.
I-Limit is usually used to try to
prevent Overload faults. See
Enhanced I-Limit on
Overload Menu-Screen 2
Coast To Stop
True
By default, the drive will
immediately release the motor
when the drive is stopped.
Recommended setting for ESP
applications is
“True”. Setting
Coast To Stop to false will cause
the drive to ramp down from
the running frequency to 0 Hz
when the drive is stopped. This
parameter may NOT be changed
while the drive is running.
Navigate between pages of the menu by pressing the Left Arrow and Right Arrow buttons. The second page
of the Drive Settings menu is shown in