Table 22: Parameters (cont'd.)
Parameter
Default
Description
Decel Seconds
5 Seconds
Time in seconds for the drive to
ramp down from Max Frequency
to 0 Hz.
For ESP applications,
maximum recommended Decel
Seconds is 10.0.
Forward/Reverse
Run Forward
Direction of Motor Rotation.
V/F Curve Select
60Hz Std Torque
Select 1 of 6 preset V/F curves.
These include Standard, Medium,
and High Torque settings for 50Hz
and 60 Hz operation. Standard
torque is default. Use medium
or high torque when faced with
a hard starting motor. Medium
and high torque settings apply a
voltage boost to the V/F curve at
low frequencies. This parameter
may NOT be changed while the
drive is running.
V/F CurveVBias
0.0 Volts
Applies a voltage bias to the
drive’s V/F curve AT MAX
FREQUENCY. The bias is linearly
interpolated at frequencies less
than Max Frequency.
DriveMaxVolts
480 Volts
Drive voltage output at Max
Frequency. This parameter may
NOT be changed while the drive
is running.
Содержание Apollo 3
Страница 1: ...Copyright 2020 Baker Hughes Company All rights reserved Page 1 of 277...
Страница 46: ...Copyright 2020 Baker Hughes Company All rights reserved Page 46 of 277 Figure 20 Backspin Probes Drawing 2...
Страница 139: ...Copyright 2020 Baker Hughes Company All rights reserved Page 139 of 277 Figure 116 Murphy Switch Trigger Example 1...
Страница 266: ...Copyright 2020 Baker Hughes Company All rights reserved Page 266 of 277 Figure 227 USB Menu...
Страница 267: ......
Страница 276: ......
Страница 277: ...Index 129112 28 197705 28 197349 28 800638 28 197350 28 810280 28 197351 29...