Figure 196: How Overload Affects Time To Overload
The screenshot above illustrates how the overload bucket drains off slowly when the current drops below
overload. In this simulation the motor is started at 125% of the overload threshold. The system detects
overload in 2 minutes and stops. The system restarts 2 minutes later with load still at 125%. The system
shuts down almost immediately (as the heat in the motor has not had time to dissipate). The system
is restarted a second time 2 minutes later with loading at 100% of overload. As you can see, at 100%
overload the motor temperature is stable.
10 Trigger Definition
10.1
Trigger Definition
Triggers are used to define events or conditions in the pumping system and to take actions that affect the
state of the motor controller (MC). When the condition is met, the trigger is said to be
SET
. If the condition is
not met, the trigger is said to be
CLEAR
. For example, a High Limit trigger tests the value of a channel
against a limit. If the limit is exceeded the trigger is SET and the system state is affected by the
ACTION
defined for the particular trigger.
Examples of Triggers:
• Tank Level High Trigger-Starts motor if a tank level exceeds the trigger limit (sometimes referred to as
setpoint or threshold).
Содержание Apollo 3
Страница 1: ...Copyright 2020 Baker Hughes Company All rights reserved Page 1 of 277...
Страница 46: ...Copyright 2020 Baker Hughes Company All rights reserved Page 46 of 277 Figure 20 Backspin Probes Drawing 2...
Страница 139: ...Copyright 2020 Baker Hughes Company All rights reserved Page 139 of 277 Figure 116 Murphy Switch Trigger Example 1...
Страница 266: ...Copyright 2020 Baker Hughes Company All rights reserved Page 266 of 277 Figure 227 USB Menu...
Страница 267: ......
Страница 276: ......
Страница 277: ...Index 129112 28 197705 28 197349 28 800638 28 197350 28 810280 28 197351 29...