4.10
Enable Autostart
By default, the ManualStartOnly parameter is set to True. The only way to start the drive when
ManualStartOnly is True is by pressing the Start button on the keypad. Change ManualStartOnly to False if
the drive should start under any other conditions. ManualStartOnly should be set to False in most systems.
Figure 96: Selecting ManualStartOnly
Table 31:
Parameter
Description
ManualStartOnly
Options:
True (default): The drive can only be started by
pressing the Start button on the keypad.
False: The drive can be started from the Start button
on the keypad, a SCADA command, a fault restart,
a power up autostart, or a Start Motor trigger.
Setting ManualStartOnly to false can initiate an automatic start without warning and may
cause equipment damage, injury to personnel or death.
4.11
Adjust Setpoint
The System Setpoint is Drive Mode dependent and is used to adjust the drive output frequency. Access the
Setpoint by pressing the Home function button on the Main Menu screen and then pressing the Settings
function button.
Содержание Apollo 3
Страница 1: ...Copyright 2020 Baker Hughes Company All rights reserved Page 1 of 277...
Страница 46: ...Copyright 2020 Baker Hughes Company All rights reserved Page 46 of 277 Figure 20 Backspin Probes Drawing 2...
Страница 139: ...Copyright 2020 Baker Hughes Company All rights reserved Page 139 of 277 Figure 116 Murphy Switch Trigger Example 1...
Страница 266: ...Copyright 2020 Baker Hughes Company All rights reserved Page 266 of 277 Figure 227 USB Menu...
Страница 267: ......
Страница 276: ......
Страница 277: ...Index 129112 28 197705 28 197349 28 800638 28 197350 28 810280 28 197351 29...