
|
126
14.6.41
Example 2 - Control TA / TP
Let's see how to set a filter on the data received in order to check the status of bits TA and TP.
For example if we want an alarm to the radio (which supports the service TA) has the TA = On for a period longer than
10 minutes.
We set the filter:
ChanRef = 4
Block1Ref = xxxxxxxxxxxxxxxx (we do not care this time of the IP)
Block2Ref = 000001XXXXX0XXXX (group 0A - TP = 1 - TA = 0)
Block3Ref = xxxxxxxxxxxxxxxx (we do not treat)
Block4Ref = xxxxxxxxxxxxxxxx (we do not treat)
Timeout = 1200s
Validation
=10s
Hold
=10s
Mask
=Unmasked
Trap
=Enabled
An alarm is generated if TA remains unchanged equal to 0 for 20 min
Starting from TP=1 and TA=0
When TA = 1, after the set time, the filter goes into alarm:
Содержание WOLF 1MS
Страница 1: ...WOLF 1MS WOLF 2MS User Manual FM monitoring system and streaming device Rev 1 3...
Страница 10: ...ENG GENERAL DESCRIPTION 10...
Страница 11: ...ENG GENERAL DESCRIPTION 11...
Страница 12: ...ENG GENERAL DESCRIPTION 12...
Страница 14: ...ENG GENERAL DESCRIPTION 14 WOLF 1MS WEB PAGE...
Страница 15: ...ENG GENERAL DESCRIPTION 15 WOLF 2MS WEB PAGE...
Страница 16: ...ENG GENERAL DESCRIPTION 16 WOLF 1MS WOLF 2MS BLOCK DIAGRAM...
Страница 78: ...78 Example 3 RFL2 MASK This schemes shows from left to right the flow of each single Alarm...
Страница 216: ...TECHNICAL APPENDIX TECHNICAL APPENDIX 216...
Страница 218: ...TECHNICAL APPENDIX TECHNICAL APPENDIX 218...
Страница 221: ...TECHNICAL APPENDIX TECHNICAL APPENDIX 221...