Multi-turn actuator

SAExC 07.1 – SAExC 16.1/SARExC 07.1 – SARExC 16.1
Non-Intrusive

with actuator controls

AUMATIC ACExC 01.1

Ex

Operation instructions

Assembly, operation, commissioning

Control:

Parallel

à

Profibus DP

Profibus DP with FO
Modbus
Modbus with FO
DeviceNet
Foundation Fieldbus

Содержание Aumatic ACExC 01.1

Страница 1: ...SARExC 07 1 SARExC 16 1 Non Intrusive with actuator controls AUMATIC ACExC 01 1 Ex Operation instructions Assembly operation commissioning Control Parallel Profibus DP Profibus DP with FO Modbus Modb...

Страница 2: ...frame 27 5 4 3 Protection cover 27 5 4 4 Ground connection external 27 6 Operation 28 6 1 Manual operation 28 6 2 Motor operation 29 6 2 1 Local operation 29 6 2 2 Operation from REMOTE 29 6 3 Menu n...

Страница 3: ...ttons do not react 57 10 2 Fault indications and warning indications 58 10 2 1 Status display S0 faults and warnings 58 10 2 2 Status indication S1 faults 59 10 2 3 Status indication S2 warnings 60 10...

Страница 4: ...horoughly read and under stood these instructions and furthermore know and observe officially recog nised rules regarding occupational health and safety Work performed in potentially explosive atmosph...

Страница 5: ...ng appliances according to EN 14502 Passenger lifts according to DIN 5306 and 15309 Service lifts according to EN 81 1 A1 Roller conveyors according to EN 14673 draft Continuous operation Buried servi...

Страница 6: ...y alert symbol warns of a potential personal injury hazard Signal word DANGER WARNING CAUTION NOTE 1 4 Further references and symbols The following references and symbols are used in these instruction...

Страница 7: ...n instructions with actuator controls AUMATIC ACExC 01 1 Profibus DP Figure 1 1 Actuator name plate 3 Motor name plate 2 Controls name plate 4 Additional plate e g KKS plate 5 Ex approval plate 1 Type...

Страница 8: ...ty Size 07 1 16 1 Version Non Intrusive Type ACExC AUMATIC actuator controls Size 01 1 Commission number An order specific commission number is assigned to each device You can use this commission numb...

Страница 9: ...and display can be performed on site directly at the con trols or alternatively from REMOTE via a fieldbus interface On site it is possible to operate the actuator via the local controls push buttons...

Страница 10: ...recycling and collection centres 10 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07 1 SARExC 16 1 Non Intrusive with actuator controls AUMATIC ACExC 01 1 Profibus DP Operation instructions Danger...

Страница 11: ...ted by approx 85 2 Attach handwheel over the red change over lever then on to the shaft 3 Secure handwheel using the circlip supplied 11 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07 1 SARExC 16...

Страница 12: ...ates uniformly in the recess and that the mounting faces are in complete contact 6 Fasten multi turn actuator with screws according to table 1 7 Fasten screws crosswise with a torque according to tabl...

Страница 13: ...ue 5 Clean the machined stem nut 6 Apply Lithium soap EP multi purpose grease to axial needle roller and cage assembly and axial bearing washers then place them on stem nut 7 Re insert stem nut with a...

Страница 14: ...alignment of the fastening holes 10 Fasten multi turn actuator with screws 3 according to table 1 page 12 11 Fasten screws crosswise with a torque according to table 1 12 Engage manual operation at mu...

Страница 15: ...tighten it firmly 3 Push down the sealing ring 3 into the housing 4 Check whether cap 1 is available and in perfect condition 15 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07 1 SARExC 16 1 Non...

Страница 16: ...ctly insert O ring 3 Turn local controls into new position and re place 4 Fasten bolts evenly crosswise 16 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07 1 SARExC 16 1 Non Intrusive with actuator...

Страница 17: ...alues for respective sizing can be derived from the current consumption of the motor plus the current consumption of the controls Motor current consumption Refer to name plate on motor nominal current...

Страница 18: ...segment If more devices are to be connected Allot devices to different segments Connect segments using repeaters Respect a distance of minimum 20 cm between the bus cable and other cables If possible...

Страница 19: ...table for connect ing cables The enclosure protection IP stated on the name plate is only ensured if suitable cable glands are used 3 Seal cable entries which are not used with suitable plugs 4 Insert...

Страница 20: ...with an additional motor heater The motor heater improves the start up behaviour for extremely low temperatures Connect motor heater R4 if available according to wiring diagram 20 Multi turn actuator...

Страница 21: ...be used to provide reliable and proper bus cable shielding Figure13 Bus connection channel 1 standard Figure14 Bus connection channel 2 for component redundancy only 21 Multi turn actuator SAExC 07 1...

Страница 22: ...ng 4 Fit cover 1 and fasten screws 2 evenly crosswise 5 Fasten cable glands with the specified torque to ensure the required enclosure protection 22 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07...

Страница 23: ...suitable for connect ing cables The enclosure protection IP stated on the name plate is only ensured if suitable cable glands are used 3 Seal cable entries which are not used with suitable plugs 4 Ins...

Страница 24: ...heater R4 if available according to wiring diagram Connect bus cables 1 Connect bus cable refer to figure 17 2 If the actuator is the final device in the bus segment Connect termination resistor for...

Страница 25: ...the sealing faces 4 Replace cover and fasten bolts evenly crosswise 5 Fasten cable glands with the specified torque to ensure the required enclosure protection 25 Multi turn actuator SAExC 07 1 SAExC...

Страница 26: ...0 5 mm manufacturer Lapp Data cable connection XM2 XA2 CAN L XM3 XA3 CAN H MWG voltage supply if the AUMATIC has been ordered and delivered with wall bracket XM6 XA6 GND XM7 XA7 24 V DC refer to wiri...

Страница 27: ...ing cage terminals KES 5 4 3 Protection cover Protection cover for plug compartment when plug is removed The open terminal compartment can be closed using a protective cover not illustrated 5 4 4 Grou...

Страница 28: ...urn handwheel into desired direction in doing so the following applies To close the valve turn handwheel clockwise Drive shaft valve turns clockwise in direction CLOSE Disengaging manual operation Man...

Страница 29: ...information on this topic refer to Manual Operation and setting AUMATIC AC 01 1 ACExC 01 1 6 2 2 Operation from REMOTE Set selector switch to position Remote control REMOTE Now it is possible to oper...

Страница 30: ...controls AUMATIC ACExC 01 1 Profibus DP Operation instructions 1 6 1 2 3 4 5 p q 8 C Figure 24 1 Push button p 4 Push button C 2 Push button q 5 Selector switch 3 Push button 8 6 Display 0 I I Push b...

Страница 31: ...ible scrolling direction within one group of scrolling Enter the password In the menu group M the settings are protected by a password To change the parameters a password must first be entered The fol...

Страница 32: ...it down for approx 3 seconds Display indicates 3 Press 8 Display indicates 4 Press q Display indicates 5 Press 8 Display indicates 6 Enter password Press 8 4 times 0000 default factory password 32 Mu...

Страница 33: ...cept value Press 8 or cancel process without accepting the value Press C 33 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07 1 SARExC 16 1 Non Intrusive Operation instructions with actuator control...

Страница 34: ...ve position display Line 3 indicates the valve position in of the travel This indication is only available if the actuator is equipped with a position transmitter 0 Actuator is in end position CLOSED...

Страница 35: ...A deflection to the right side indicates torque in direction OPEN Example SA 07 5 with 20 60 Nm 100 corresponds to 60 Nm of nominal torque 50 corresponds to 30 Nm of nominal torque Information The tor...

Страница 36: ...g indication indicates that the end positions via indication mark have been reached 36 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07 1 SARExC 16 1 Non Intrusive with actuator controls AUMATIC AC...

Страница 37: ...ntact default value Designation in the wiring diagram NC fault NO ready FAULT GROUP 3 fault signal includes Torque fault thermal fault phase failure and internal faults Standard values output contacts...

Страница 38: ...hat for low temperature versions the controls require a heat up time Heat up time This heat up time is applicable in case the actuator and the controls are not live and have cooled down to ambient tem...

Страница 39: ...FAULTS or TSC FAULTS menu S1 Via the menu to parameter MAIN MENU M0 SETTINGS M1 SEATING MODE M11 VIEW M110 EDIT M111 OPEN POSITION M11_0 CLOSED POSITION M11_1 Default value LIMIT Step by step 1 Set th...

Страница 40: ...nd CLOSED POSITION right figure displays 10 Back to the VIEW EDIT menu Press C twice Change setting Display indicates 11 Press q 40 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07 1 SARExC 16 1 No...

Страница 41: ...l process without accepting the value Press C Display indicates 18 Return to status display Press C several times until S0 is displayed 41 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07 1 SARExC...

Страница 42: ...ndicates 4 Press 8 Display indicates 5 Press q twice Display indicates 42 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07 1 SARExC 16 1 Non Intrusive with actuator controls AUMATIC ACExC 01 1 Prof...

Страница 43: ...ht figure displays 10 Back to the VIEW EDIT menu Press C twice Change setting Display indicates 11 Press q Display indicates 12 Press 8 Display indicates 43 Multi turn actuator SAExC 07 1 SAExC 16 1 S...

Страница 44: ...d Information The following fault signals are sent if torque setting performed has been reached in mid travel Status indication S0 FAULT IND Status indication S1 TORQUE FAULT OPEN or TORQUE FAULT CLOS...

Страница 45: ...The current actuator position is displayed p q are used to change between the CLOSED POSITION left figure and OPEN POSITION right figure displays 45 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07...

Страница 46: ...ngage manual operation 15 Turn handwheel counterclockwise until valve is open 16 Turn handwheel back by approximately half a turn overrun 17 Press 8 to accept new end position LEDs and display indicat...

Страница 47: ...setting the selector switch must be in position 0 OFF 47 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07 1 SARExC 16 1 Non Intrusive Operation instructions with actuator controls AUMATIC ACExC 01...

Страница 48: ...DP 1 M1B Press q several times Display indicates 6 Press 8 Display indicates 7 Check setting view continue with 8 Change setting continue with 11 48 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07...

Страница 49: ...4 times 0000 default factory password Display indicates 14 Press 8 49 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07 1 SARExC 16 1 Non Intrusive Operation instructions with actuator controls AUM...

Страница 50: ...on the bus address for the 2nd fieldbus interface can be set in the same way as the 1st field interface The menu for the second fieldbus interface has to be selected from the descriptions Via the menu...

Страница 51: ...n For actuators equipped with indicator disc Observe direction of rotation on the indicator disc The direction of rotation is correct if The actuator moves in direction CLOSE while the indicator disc...

Страница 52: ...SED The green indication light LED5 is illuminated in end position OPEN The limit switching is set incorrectly if The actuator comes to a standstill before reaching the end position One of the red ind...

Страница 53: ...p mark on the cover 5 Move valve to end position CLOSED again 6 Check settings If the symbol CLOSED is no longer in alignment with p mark on the cover Test set gear stage of the reduction gearing page...

Страница 54: ...e with point 4 If the setting is correct continue with point 7 54 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07 1 SARExC 16 1 Non Intrusive with actuator controls AUMATIC ACExC 01 1 Profibus DP...

Страница 55: ...dicator disc on shaft 8 Set the mechanical position indicator as described on page 53 55 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07 1 SARExC 16 1 Non Intrusive Operation instructions with act...

Страница 56: ...4 Check whether O ring 3 is in good condition correctly insert O ring 5 Place cover 1 on switch compartment 6 Fasten screws 2 evenly crosswise 56 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07 1...

Страница 57: ...standstill 2 Set limit switching again page 45 considering the overrun turn handwheel back by the amount of the overrun 10 1 3 Push buttons do not react Fault description Push buttons do not react Th...

Страница 58: ...ormation press qp and go to status indications S1 faults or S2 warnings NOT READY IND The actuator cannot be operated from REMOTE The actuator can only be operated via the local controls For further i...

Страница 59: ...lector switch to position Local control LOCAL and reset fault indication via Reset push button or Issue reset command via fieldbus LOSS OF PHASE One phase is missing Test connect phases THERMAL FAULT...

Страница 60: ...ccurred For further information 1 Go to group D0 Press C and hold it down until diagnostic indication D0 is displayed 2 Go to diagnostic indication D3 Press q three times FEEDBACK E2 LOSS Signal loss...

Страница 61: ...PID controller is available and active Check wiring FIBER OPTIC LOSS Signal loss of FO cable for bus with FO loop topology only Check wiring ANALOG IN1 BUS1 LOSS Signal loss of analogue input 1 Check...

Страница 62: ...G COMMAND Indicates the fact that several operation commands were received simulta neously via Profibus DP e g Remote OPEN and Remote CLOSE simulta neously or Remote CLOSE Remote OPEN and Remote SETPO...

Страница 63: ...ator controls AUMATIC ACExC 01 1 Profibus DP Figure 30 Flameproof enclosure danger of explosion Risk of death or serious injury Before opening ensure that there is no explosive gas and no voltage Hand...

Страница 64: ...S0 S6 operation mode REMOTE FAULT IND Status indication S1 in the display THERMAL FAULT The motor has to cool down before the operation can be resumed Depending on the parameter setting the fault sign...

Страница 65: ...se gun quantities see 13 table 2 This procedure does not grease the valve stem Lubrication of the valve stem must be done separately 6 months after commissioning and then once a year Check screws betw...

Страница 66: ...O ring is in good condition correctly insert O ring 4 Preserve joint surfaces with an acid free corrosion protection agent 5 Replace plug socket connector and fasten bolts evenly crosswise 66 Multi t...

Страница 67: ...ouration of the terminals and wires This would indicate an increased temperature For Ex housings pay special attention to a possible collection of water This may originate from breathing due to severe...

Страница 68: ...llowing generally applies Collect greases and oils during disassembly Generally these sub stances are hazardous to water and must not be released into the envi ronment Arrange for controlled waste dis...

Страница 69: ...Notes 69 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07 1 SARExC 16 1 Non Intrusive Operation instructions with actuator controls AUMATIC ACExC 01 1 Profibus DP...

Страница 70: ...Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07 1 SARExC 16 1 70 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07 1 SARExC 16 1 Non Intrusive with actuator controls AUMATIC ACExC 01 1 Profibus...

Страница 71: ...et B3 B4 E 551 1 Parallel key 553 0 Mechanical position indicator Sub assembly 554 0 Socket carrier with motor cable harness Sub assembly 556 0 Potentiometer for position transmitter Sub assembly 556...

Страница 72: ...1 1 with ex plug socket connector with terminal board KP KPH 72 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07 1 SARExC 16 1 Non Intrusive with actuator controls AUMATIC ACExC 01 1 Profibus DP Op...

Страница 73: ...Pin for motor Sub assembly 507 0 Plug cover Sub assembly 508 0 Switchgear Sub assembly 509 1 Padlock 510 0 Fuse kit Set 532 0 Line bushing actuator connection Sub assembly 535 1 Circlip S Seal kit Set...

Страница 74: ...s ACExC 01 1 with ex plug in terminal connection KES 74 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07 1 SARExC 16 1 Non Intrusive with actuator controls AUMATIC ACExC 01 1 Profibus DP Operation...

Страница 75: ...29 0 End piece 532 0 Line bushing actuator connection Sub assembly 533 0 Terminals for motor controls 535 1 Circlip 573 0 Plug in electrical connection Sub assembly S Seal kit Set 75 Multi turn actuat...

Страница 76: ...ater option SAExC SARExC 07 1 10 1 12 5 W SAExC SARExC 14 1 16 1 25 W Manual operation Manual drive for setting and emergency operation handwheel does not rotate during electrical operation Option Han...

Страница 77: ...s Component redundancy option AUMATIC is equipped with an additional redundant Profibus DP interface Local controls Standard Selector switch LOCAL OFF REMOTE lockable in all three positions Push butto...

Страница 78: ...definable customer fields with a max of 19 digits each Service data Service telephone Internet address service text 1 service text 2 Logging of operating data A resettable counter and a lifetime count...

Страница 79: ...switch tripped in mid travel One phase missing Loss of analogue customer inputs Behaviour on loss of communication The behaviour of the actuator is programmable Stop in current position Move to end p...

Страница 80: ...om this Applies to actuator with actuator controls only not valid in combination with gearboxes Lifetime Open study duty Operating cycles OPEN CLOSE OPEN SAExC 07 1 SAExC 10 1 20 000 SAExC 14 1 SAExC...

Страница 81: ...Declaration of Conformity and Declaration of Incorporation 81 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07 1 SARExC 16 1 Non Intrusive Operation instructions with actuator controls AUMATIC ACE...

Страница 82: ...14 2 PTB certificate 82 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07 1 SARExC 16 1 Non Intrusive with actuator controls AUMATIC ACExC 01 1 Profibus DP Operation instructions...

Страница 83: ...83 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07 1 SARExC 16 1 Non Intrusive Operation instructions with actuator controls AUMATIC ACExC 01 1 Profibus DP...

Страница 84: ...84 Multi turn actuator SAExC 07 1 SAExC 16 1 SARExC 07 1 SARExC 16 1 Non Intrusive with actuator controls AUMATIC ACExC 01 1 Profibus DP Operation instructions...

Страница 85: ...eration 28 Mechanical position indicator 53 Motor heater 20 24 Motor operation 29 Motor protection 64 Mounting 12 Mounting positions of the local controls 16 O Operation 28 Output drive type A 13 Outp...

Страница 86: ...ellos gr SIGURD S RUM A S NO 1300 Sandvika Tel 47 67572600 Fax 47 67572610 post sigurd sorum no INDUSTRA PT 2710 297 Sintra Tel 351 2 1910 95 00 Fax 351 2 1910 95 99 industra tyco valves com MEGA End...

Страница 87: ...ols Co Ltd KR 153 803 Seoul Korea Tel 82 2 2113 1100 Fax 82 2 2113 1088 1089 sichoi actuatorbank com www actuatorbank com Sunny Valves and Intertrade Corp Ltd TH 10120 Yannawa Bangkok Tel 66 2 2400656...

Страница 88: ...00 104 4269 AUMA Riester GmbH Co KG P O Box 1362 D 79373 M llheim Tel 49 7631 809 0 Fax 49 7631 809 1250 riester auma com www auma com For detailed information on AUMA products refer to the Internet w...