TeleBoss 850 2.06.280_STD User Manual
Page 1
Quick Start
What's Included
This chapter is a brief guide to help get your TeleBoss 850 (T850) up and running quickly.
Hardware Needed
Asentria TeleBoss 850
15VDC power adaptor (Included if AC power option)
DC power source (if DC power option)
Computer with serial port and terminal emulation software, and/or network access.
Ethernet cable
RJ45 M-M unshielded serial cable and RJ45/DB9 straight thru adapter (Included)
A PC running any type of SNMP trap management software, if T850 will be sending SNMP traps as event actions.
Information Needed
IP address(es) to assign to the T850
Subnet mask
Default router IP or gateway router IP address if on a WAN (Optional)
IP address of a PC running any type of SNMP trap management software, if T850 will be sending SNMP traps as
event actions.
Physiclly Install TeleBoss
Note:
THIS PRODUCT MUST BEINSTALLED WITHIN A RESTRICTED ACCESS LOCATION WHERE ACCESS
IS THROUGH THE USE OF A TOOL, LOCK AND KEY, OR OTHER MEANS OF SECURITY, AND IS
CONTROLLED BY THE AUTHORITY RESPONSIBLE FOR THE LOCATION.
Ensure conditions A-E will be met by the installation before proceeding.
A) Elevated Operating Ambient - If installed in a closed or multi-unit rack assembly, the operating ambient
temperature of the rack environment may be greater than room ambient. Therefore, consideration should be given to
installing the equipment in an environment compatible with the maximum ambient temperature (Tma), which is 40C
for standard units 65C for extended temperature units.
B) Reduced Air Flow- Installation of the equipment in a rack should be such that the amount of air flow required for
safe operation of the equipment is not compromised.
C) Mechanical Loading - Mounting of the equipment in the rack should be such that a hazardous condition is not
achieved due to uneven mechanical loading.
D) Circuit Overloading - Consideration should be given to the connection of the equipment to the supply circuit and
the effect that overloading of the circuits might have on overcurrent protection and supply wiring. Appropriate
consideration of equipment nameplate ratings should be used when addressing.
E) Reliable Earthing -Reliable earthing of rack-mounted equipment should be maintained. Particular attention should
be given to supply connections other than direct connections to the branch circuit (e.g.use of power strips).
Physically install the SiteBoss into your site. Use the included Mounting Brackets to secure to a standardly grounded
equipment rack.
If the unit is not mounted within a grounded rack system, connect the attached ground wire securely to an appropriate
earth ground.
Connect an Ethernet cable into the RJ45 jack labeled ETH1.