TeleBoss 850 2.06.280_STD User Manual
Page 122
EventSensor™ Configuration Setup
The T850 can be ordered with any of the following different internal I/O devices or can be connected to a number of
external EventSensor or SensorJack devices as described in this section. The setup menus are the same regardless
of whether the device is internal or external to the T850. If using external EventSensor or Sensor Jack sensors with
the T850, please refer to the EventSensor User Manual or SensorJack Sensor User Guide for a full description of
each type of sensor, and hardware specifications.
Input
Output
Virtual (
via Scripting only)
EventSensor ID: ESIO00999
Name: unnamed
Contact Closure States:
01 unnamed Open
02 unnamed Open
03 unnamed Open
04 unnamed Open
05 unnamed Open
06 unnamed Open
07 unnamed Open
08 unnamed Open
Above is a representative Internal Events Menu showing an ES-8C Type 2 EventSensor that features 8 contact
closures. Descriptions of temperature, humidity, voltage and relays will follow.
displays the menu for configuring each of the contact closure points.
Contact Closure Setup
TeleBoss 850 - Internal Contact Closure Event 1
A) Sensor Name [unnamed]
B) Contact Closure Enabled [OFF]
C) Event State [OPEN]
D) Threshold [2]
E) Event State Actions []
F) Return to Normal Actions []
G) Event State Class [Info]
H) Return to Normal Class [Info]
I) Event Trap Number [110]
J) Return to Normal Trap Number [110]
K) Active Alarm Alias []
L) Inactive Alarm Alias []
Contact closures (CC) sense the state of a circuit. A weak voltage is applied to the source pin and if pulled to ground
by a connection on the circuit, the sensor reports a "closed" state. If it remains high, the sensor reports an "open"
state. All of the CCs share a common ground. The contact closures may be configured to alarm in either the open or
closed state, depending on the needs of the attached devices.
Sensor Name
is an alphanumeric field that allows you to name this contact closure. (Max length 16 chars)
Contact Closure Enabled
is an ON/OFF toggle to enable this contact closure. Default setting is OFF.