TeleBoss 850 2.06.280_STD User Manual
Page 213
Rev F
On-board ESJ/ES (Type 3B) port:
EventSensors (Type1) / CCU32/64 (Type1)
Yes. Connect sensor to Serial Port I/O1 set to ESBUS mode, with an RS232/ES Bus Adapter (part #4162-010).
PB1
No
EventSensor (Type2) / ES-CCU32/64 (Type2)
Yes, connect sensor to on-board ESJ/ES port with an RJ45/RJ45 cable. If the unit also has a 4SJ expansion card
installed, then the on-board sensor port is disabled. Connect the sensor to one of the 4SJ ports instead.
PB2
Yes, requires the T850 host to be running version 2.06.290 or higher. Also, a PB2 is only supported by an on-
board sensor port, so it will not work if connected to a 4SJ port.
SensorJack (Type3)
Yes. These sensors terminate with an RJ45 plug so connect directly to the ESJ/ES port. If using multiple Sensor
Jack sensors, or with EventSensor (Type2) sensors, use an RJ45 Splitter (part# 4162-011).
Note: Currently only the SensorJack Temp Sensor is supported by the T850. Support for the SensorJack
Temp/Humidity sensor will be coming soon.
Daisy-chaining a SensorJack sensor to an EventSensor (Type2) sensor does not work. The SensorJack sensor
must be connected directly to the ESJ/ES port, or to an RJ45 Splitter that routes directly to the port (through other
RJ45 splitters is OK).
EventSensor (Type1) sensors cannot be daisy-chained with EventSensor (Type2) sensors; however you can use
EventSensor (Type1) sensors connected to Serial Port I/O1
and
EventSensor (Type2) sensors connected to any
sensor port simultaneously. Just make sure the DIP Switches on all are set so that there are no slotting conflicts.
Содержание Teleboss 850