Analog voltage sensors provide individual voltage sensing for ranges from
–60/+60VDC.
Analog current sensors provide individual voltage sensing for ranges from 4-20mA.
Note:
Effective with firmware version 2.05.840, the analog value has changed from 16-bit to 32-bit, which
increases range of unit value to +2147483647 and
–2147483648. Now all analog voltage slot cards, including 4VP,
can -60 volts and still maintain accuracy and resolution at lower voltage inputs.
Device Name
is the option name given to the sensor. Default is unnamed.
displays a menu where each analog voltage sensor can be configured.
Event Sensor Reporting Enabled
is an ON/OFF toggle to enable the Event Sensor Reporting feature. See the
section in the Features chapter for more information.
Clear Settings for This EventSensor
when selected will immediately clear all of the configured settings for this
sensor and remove it from the Sensor Events menu (except for Internal Sensors). If "Confirmation Prompt“ in General
Settings is ON, then there will be a confirmation prompt (
Are you sure (y/n)?
) displayed before clearing the
configured settings. Return to the Sensor Events menu to assign it a new slot, if desired, and reconfigure it.
Analog Input
n
TeleBoss 850 Internal Analog Input Event 1
Device Number: 1 Device ID: 20020000 Device Name:
A) Analog Input Enabled [OFF]
B) Name [ ]
C) Input Polarity [POSITIVE]
D) Deadband [30]
E) Very High Event Settings [600] [] [140] [Info]
F) High Event Settings [600] [] [140] [Info]
G) Return to Normal Settings [-] [] [140] [Info]
H) Low Event Settings [0] [] [140] [Info]
I) Very Low Event Settings [0] [] [140] [Info]
J) Unit Conversion Settings [Volts]
Analog Input Enabled
is an ON/OFF toggle to enable this analog sensor. Default setting is OFF.
Name
is an alphanumeric field that allows you to name this analog input. (Max length 16 chars)
Input Polarity
indicates to the unit whether the input polarity will be positive or negative.
Deadband
is the range on either side of an analog setting that prevents the alarm from repeatedly going in and out off
the "alarm state" as the actual voltage or current fluctuates above and below the setting.
Very High / High / Low / Very Low Event Settings
displays a menu where the voltage or current at each level can
be configured to alarm along with the action(s) to occur, trap number, and class. In the case of Very High or High
levels, the alarm will occur as the voltage or current rises above the setting. In the case of Low or Very Low, the alarm
will occur as the voltage or current drops below the setting.
displays a menu where the optional action definition for alarms as they return to a normal
state can be configured.
displays a menu where “real world” values can be configured.