TeleBoss 850 2.06.280_STD User Manual
Page 127
Very High / High / Low / Very Low Analog Input Event Settings
TeleBoss 850 Internal Analog Input Event Settings
Device Number: 1 Device ID: 20020000 Device Name:
A) Very High Event Value [600]
B) Very High Event Actions []
C) Very High Event Trap Number [140]
D) Very High Event Class [Info]
The menu for setting Very High Event Value settings is shown. Menus for High/Low/Very Low are identical.
Very High Event Value
sets the voltage or current (in tenths) at which the Very High Event Actions will be triggered.
Very High Event Actions
displays the Actions List, a menu where the action string for the event is configured. This
field will be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have been
configured. Refer to
in the Features chapter for more information.
Very High Event Trap Number
sets the trap number which can be useful when using SNMP trap managers that
employ a trap numbering system to help identify incoming traps. The default trap number for Analog Events is 140,
but any number in the alternate range of 1000
– 1199 can be used.
Very High Event Class
sets the class for the alarm. When this option is selected, a list of the classes previously
is displayed, from which you can select one to be assigned to this event.
Return to Normal Settings
TeleBoss 850 Internal Analog Input Event Settings
Device Number: 1 Device ID: 20020000 Device Name:
A) Return to Normal Event Actions []
B) Return to Normal Event Trap Number [140]
C) Return to Normal Event Class [Info]
Return to Normal Event Actions
displays the Actions List, a menu where the action string for the event is
configured. This field will be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions
have been configured. Refer to
in the Features chapter for more information.
Return to Normal Event Trap Number
sets the trap number which can be useful when using SNMP trap managers
that employ a trap numbering system to help identify incoming traps. The default trap number for analog events is
140, but any number in the alternate range of 1000
– 1199 can be used.
Return to Normal Event Class
sets the class for the alarm. When this option is selected, a list of the classes
previously defined in the
is displayed, from which you can select one to be assigned to this event.
Unit Conversion Settings
TeleBoss 850 Analog Input Event Unit Conversion
Device Number: 1 Device ID: 20020000 Device Name:
A) Unit Name [Volts]
B) Low Voltage Amount (tenths) [0]
C) Low Unit Amount (tenths) [0]
D) Low Unit Sign [POSITIVE]
E) High Voltage Amount (tenths) [600]
F) High Unit Amount (tenths) [600]
G) High Unit Sign [POSITIVE]