TeleBoss 850 2.06.280_STD User Manual
Page 44
Data Alarm/Filter Settings
TeleBoss 850 - Data Alarm/Filter Settings
A) Alarm/Filter Page 1 (Alarms 1-16)
B) Alarm/Filter Page 2 (Alarms 17-32)
...
P) Alarm/Filter Page 16 (Alarms 241-256)
Q) Next Page Selection Screen
Data alarms are configured by selecting an option from the main Data Alarm/Filter Settings menu, then selecting one
of the options which will give you a group of 16 data alarm/filters (1-16, 17-32, etc) or selecting the Next or Previous
Page Selection Screen. This will display a menu where you can select from those 16 data alarm options as follows:
TeleBoss 850 - Data Alarm/Filter Settings
A) Alarm/Filter 1 [] [OFF] [ALARM]
...
P) Alarm/Filter 16 [] [OFF] [ALARM]
Q) Next Alarm/Filter Page
R) Setup Alarm/Filter Fields
S) Display Alarm Status
T) Exit Upon True Data Alarm [OFF]
Enter your Selection:
displays the menu where an individual data alarm or filter can be configured.
Next or Previous Alarm/Filter Page
displays either the next or previous set of 16 Data Alarm/Filters.
Setup Alarm/Filter Fields
menu as described above. This is simply
an easy way to access that menu without having to exit back through the previous menus.
Display Alarm Status
displays real time information on data event monitors you've configured.
Exit Upon True Data Alarm
is an ON/OFF toggle to set whether the T850 will stop processing more data event
evaluations on a single record after it has found one match. This should be disabled if it is possible to have more than
one event in a record. This is a global setting
– it applies to ALL configured data alarms. Default setting is OFF.
Data Alarm/Filter
n
Settings
TeleBoss 850 - Settings For Data Alarm/Filter 1
A) Alarm/Filter Enable [OFF]
B) Alarm/Filter Mode [ALARM]
C) Alarm/Filter Name []
D) Alarm/Filter Equation []
E) Threshold [1]
F) Auto-Clear when Threshold Reached [ON]
G) Alarm Counter Clear Interval [12 HOURS]
H) Alarm Counter Reset Time [00:00]
I) Actions []
J) Class [Info]
K) Data Alarm Trap Number [503]
L) Clear This Alarm Counter Now
Alarm/Filter Enable
is an ON/OFF toggle for each individual data event monitor. Default setting is OFF.
Alarm/Filter Mode
toggles between Alarm and Filter to indicate whether the T850 will recognize this data event as an
Alarm and take some action, or as a Filter and either accept or reject the data string. Default setting is ALARM.