TeleBoss 850 2.06.280_STD User Manual
Page 52
CPE Alarm Settings
TeleBoss 850 - CPE Alarm Settings
A) Alarm Enable [OFF]
B) Alarm Actions []
C) Alarm Trap Number [511]
D) Alarm Class [Info]
E) Return to Normal Actions []
F) Return to Normal Trap Number [511]
G) Return to Normal Class [Info]
These settings are only for use with Customer Premises Equipment (CPE) managed via the Asentria SitePath secure,
unified administration portal software. Contact
Alarm Enable
is an ON/OFF toggle to enable the CPE Down Event. Default setting is OFF.
Alarm Actions
displays the Actions List, a menu where the action string for the event is configured. This field will be
empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have been configured.
Refer to
in the Features chapter for more information.
Alarm Trap Number
sets the number to be sent with any SNMP traps for this event. Default is 511, but trap number
can also be set in the range of 1000
– 1199 as needed.
Alarm Class
sets the class for the alarm. When this option is selected, a list of the classes previously defined in the
is displayed, from which you can select one to be assigned to this event.
Return to Normal Actions
displays the Actions List, a menu where the action string for the event is configured. This
field will be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have been
configured. Refer to
in the Features chapter for more information.
Return to Normal Trap Number
sets the trap number which can be useful when using SNMP trap managers that
employ a trap numbering system to help identify incoming traps. The default trap number for CPR Down Events is
511, but any number in the alternate range of 1000
– 1199 can be used.
Return to Normal Class
sets the class for the alarm. When this option is selected, a list of the classes previously
is displayed, from which you can select one to be assigned to this event.
Event Message Settings
TeleBoss 850 - Event Message Settings
A) Include Date and Time [ON]
B) Include Site Name [ON]
C) Include Sensor ID [ON]
D) Include User Defined Name [ON]
E) Include User Defined State [ON]
F) Include Event Class [OFF]
Include Date and Time / Site Name / Sensor ID / User Defined Name / User Defined State / Event Class
are each
ON/OFF toggles to permit customization of the event message that appears in SNMP traps, Emails, SMS messages,
pages, etc. sent by the T850. Default setting for each is ON, except for Include Event Class which defaults to OFF.