TeleBoss 850 2.06.280_STD User Manual
Page 48
Schedule
n
Duration
is the number of minutes (0-65535) the unit will wait without receiving data before alarming.
Apply Alarm on Days
displays a menu where the seven days of the week are listed, and each can be toggled ON or
OFF to designate whether this particular No-Data alarm is active on that day. Default setting is ON for Monday thru
Friday, and OFF for Saturday and Sunday.
Enable Ports
displays a menu where the installed serial ports are listed and each can be toggled ON or OFF to
designate whether this particular No-Data alarm is active on that port. Default setting is OFF for all ports.
Add Exclusion / Delete Exclusion
allow you to add or delete specific dates when this No-
Data Alarm should “take
the day off”. For example, Christmas is a day you might want to add here. Select Add Exclusion and type in
12/25
.
To delete a date, you select Delete Exclusion and type in the date you want to remove. After an exclusion date is
added it appears in the brackets at the bottom of the menu. 15 dates can be entered to be excluded.
Percent Full Alarm Settings
TeleBoss 850 - Percent Full Alarm Settings
A) Alarm Enable [OFF]
B) Percent Full Threshold [80]
C) Alarm Actions []
D) Alarm Message [DB Exceeds Threshold]
E) Alarm Class [Info]
F) Trap Number [501]
Alarm Enable
is an ON/OFF toggle to enable the percent full alarm. Default setting is OFF.
Percent Full Threshold
set the percent full level at which the alarm will be triggered. Default setting is 80 percent.
Alarm Actions
displays the Actions List, a menu where the action string for the event is configured. This field will be
empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have been configured.
Refer to
in the Features chapter for more information.
Alarm Message
sets the text string to be delivered with the percentage full alarm. Default setting is DB Exceeds
Threshold. (Max length 111 chars)
Alarm Class
sets the class for the alarm. When this option is selected, a list of the classes previously defined in the
is displayed, from which you can select one to be assigned to this percent full alarm.
Trap Number
sets the number to be sent with any SNMP traps for this event. Default is 501, but trap number can
also be set in the range of 1000
– 1199 as needed.
Scheduled Event Settings
Scheduled Events allow you to schedule specific a specific date/time for an alarm action to occur. For example, you
might want the T850 to send you an Email every morning at 8:00 just so you know it is live on the network.