TeleBoss 850 2.06.280_STD User Manual
Page 110
11. Select Alarm/Filter Equation and enter
TEST_FIELD="test”
. This will cause an event to occur any time the word
"test" is received.
12. Select Actions and enter "
TRAP(1)
" to cause this data event to send a trap to SNMP manager #1, as configured
below in the Hostname/IP Address menu.
Other Setup
1.
Return to the Main Setup Menu, select “Action Definitions”, select “Hostname/IP Address 1” and enter either the
hostname or IP address of the SNMP Manager where the trap will be sent.
2. Go to the Serial Setup Menu for serial port I/O 1 (or whichever port incoming data will be monitored) and set the
Data Alarm Enable setting to ON.
3. Press <CTRL> + C to return to the command processor.
Testing
Connect to the unit serially on I/O 1 and type the word
test
followed by <Enter>. This should trigger the above data
event, and an SNMP trap should be sent to SNMP Manager #1. If this is not the case, double check the network and
data event settings and then call
Note:
There will be a 30 second delay in alarming if the terminal emulator being used does not send a LF with the
CR. This may be circumvented by pressing <CTRL + J> to generate a LF.