TeleBoss 850 2.06.280_STD User Manual
Page 47
Sensor Unresponsive Timeout
sets the time (10 - 65535 seconds) to wait before declaring a non-communicative
EventSensor unresponsive. Default setting is 30.
Sensor Unresponsive Actions
displays the Actions List, a menu where the action string for the event is configured.
This field will be empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have been
configured. Refer to
in the Features chapter for more information.
Sensor Unresponsive Trap Number
sets the number to be sent with any SNMP traps for this event. Default is 50,
but trap number can also be set in the range of 1000
– 1199 as needed.
Sensor Unresponsive Class
sets the class for the alarm. When this option is selected, a list of the classes
previously defined in the
is displayed, from which you can select one to be assigned to this event.
No-Data
n
Alarm Settings
No Data Alarms can be configured on the T850 to monitor data coming in via the serial ports, and take an alarm action
if a certain period of time passes with no data.
TeleBoss 850 - No-Data Alarm 1 Settings
A) Alarm Enable [OFF]
B) Alarm Actions []
C) Alarm Message [No-Data Timeout 1]
D) Alarm Class [Info]
E) Trap Number [505]
F) Schedule 1 Begin Time [00:00]
G) Schedule 1 End Time [00:00]
H) Schedule 1 Duration (minutes) [0]
I) Schedule 2 Begin Time [00:00]
J) Schedule 2 End Time [00:00]
K) Schedule 2 Duration (minutes) [0]
L) Apply Alarm on Days [MTuWThF]
M) Enable Ports
N) Add Exclusion
O) Delete Exclusion
[]
[]
No-Data
n
Alarm Settings
allows you to configure two separate No-Data Alarms, each of which can be configured for
two different ranges of times with different time durations. The periods of time should be configured to match the
calling patterns of your business or organization. For example, if your normal business hours are M-F 8:00 to 5:00,
you will want to set lower time durations during those hours than you would “after hours” when call volumes are lighter
and the periods of time where there is "
no data“ might be longer.
Alarm Enable
is an ON/OFF toggle to enable the no-data monitor. Default setting is OFF.
Alarm Actions
displays the Actions List, a menu where the action string for the event is configured. This field will be
empty [ ] if no actions have been configured, and will show [*SET*] if one or more actions have been configured.
Refer to
in the Features chapter for more information.
Alarm Message
sets the text string to be delivered with this
event’s alarms. Default setting is "No-Data Timeout
n
“.
(Max length 126 chars)
Alarm Class
sets the class for the alarm. When this option is selected, a list of the classes previously defined in the
is displayed, from which you can select one to be assigned to this event.
Trap Number
sets the number to be sent with any SNMP traps for this event. Default is 505, but trap number can
also be set in the range of 1000
– 1199 as needed.
Schedule
n
Begin Time / End Time
sets the beginning and ending times (24 hr clock) for each of two ranges of time.