TeleBoss 850 2.06.280_STD User Manual
Page 22
Enable EventSensor Reporting Host
is an ON/OFF toggle to enable this T850 to be a host for EventSensor
reporting from another Asentria device. Default setting is OFF.
EventSensor Reporting Host Port
sets the TCP Port that this T850 will use for receiving sensor reports from
another Asentria device. Default setting is 4000.
For a further explanation of EventSensor Reporting, refer to the
chapter
SNMP Settings
TeleBoss 850 - SNMP Settings
A) SNMP Community [public]
B) Trap Settings
C) Security Method [MD5-DES]
D) PPP/Trap IP Address Spoofing [0.0.0.0]
SNMP Community
sets the SNMP community name to use. Default setting is Public. (Max length is 23 chars)
displays a menu that allows you to configure various Notification settings.
Security Method
toggles between MD5-DES and SHA-AES to controls whether MD5 and DES, or SHA-1 and AES,
are used for authentication and privacy, respectively, for for SNMPv3 get/set/trap operations. Default setting is MD5-
DES.
PPP/Trap IP Address Spoofing
allows you to configure the IP address to be displayed in an SNMP trap sent over a
PPP connection. If undefined, the T850 PPP IP is used. Default setting is 0.0.0.0
Trap Settings
TeleBoss 850 - Trap Settings
A) Notification Attempts (0=infinite) [5]
B) Notification Timeout (seconds) [60]
C) Notification Cycles (0=infinite) [10]
D) Notification Snooze Period (minutes) [60]
E) Notification Security Name []
F) Notification Security Password [********]
Notification Attempts
sets the number of attempts (1 to 65535) of sending a notification (trap/inform) per cycle (that
is, the initial a retries). If this is 0 then there is 1 infinite cycle. Default setting is 5.
Notification Timeout
sets the number of seconds (3 to 60) between two attempts to send an SNMP notification in the
same cycle. Default setting is 60.
Notification Cycles
sets the maximum number of cycles (0 to 60) to try per notification action, where one notification
action corresponds to one "inform" keyword in an action list for an event. A cycle is a set of notification attempts
delimited by a successful action delivery or snooze period. Default setting is 10.
Notification Snooze Period
sets the time in minutes (1 to 1440) between two SNMP notification cycles for any one
notification action. That is, if you have two events generate informs, each inform will have its own timeouts for retries
and cycles, and its own snooze period. Default setting is 60.
Notification Security Name / Password
sets the name and password used for authentication when sending
SNMPv3 traps. (Max length for each is 31 chars)
Note:
SNMP traps are
not
a guaranteed means of delivering notifications. Traps are a one-way IP network
datagram and the device receiving traps does not acknowledge them. Therefore, if the trap does not reach its
intended destination for whatever reason, the sending device has no way of recognizing this and resending the trap.
Содержание Teleboss 850