Setup
Page 50 of 178
Figure 3.44
–
ControlNet Map configuration
The ControlNet Map configuration consists of the following parameters:
Parameter
Description
Device
The device instance name configured in the previous ControlNet Devices tab.
The selected device will be used for executing the communication function.
Function
The user can select one of four functions.
Get
The module will read data from the target ControlNet device by using the Get Single
Attribute CIP function. The received data will be placed into the Internal Data Space at
the
Input Offset
location configured in this tab.
Set
The module will write data to the target ControlNet device by using the Set Single
Attribute CIP function. The data to be written will be retrieved from the Internal Data
Space at the
Output Offset
location configured in this tab.
Set Static
Similar to the Set function above, but the data to be written will be fixed (equal to the
Static Value
) parameter in this configuration window. This function will typically be
used with the single (
S
) Scan class which means the ControlNet Router module can be
setup to write the fixed value only once when the target device communication has
been established.
Custom
This function allows the user to use a custom Service to write and read data in the
same transaction. The user will need to see which custom services that target device