Setup
Page 85 of 178
Device Type
The Device Type of the target device.
Product Code
The Product Code of the target device.
Major Revision
The Major Revision of the target device.
Minor Revision
The Minor Revision of the target device.
Advanced (Note: Changing these values is not recommended)
Tick Time
For unconnected messages, this is the time for each tick to calculate the
unconnected Time-Out time.
Time-Out Ticks
The number of ticks before the unconnected message is set for timeout.
Time-Out Multiplier
This is the multiplier of the RPI to define the connection timeout time.
Time-Out
The unconnected message timeout time (read-only)
Transport Trigger Direction
The Transport Trigger direction;
Server
or
Client
.
Configuration
Data
The configuration data that is sent with the forward open connection
establishment. The data will need to be entered as a space-delimited,
hexadecimal string. For example: 0A 0D 12 EE
The configuration size will increase by one each time a byte is added to the
configuration.
Table 3.13
–
EtherNet/IP Class 1 Connection Parameters
B.
IMPORT TOOL
PREPARATION
Before the connection information can be imported some preparation is required using
Studio5000 and a Logix controller:
1.
In Studio5000 create a new project and add the required EtherNet/IP device in the IO tree. If
the device’s profile supports configuration, then configure the device as required.
2.
Download the project to a Logix controller.
NOTE:
When instantiating modules in Studio5000 do not make use of the
“Rack Optimization” communication format.
NOTE:
Some versions Logix (V32+) do not support the reading of the module’s
configuration. Where possible use an earlier version (e.g. V24).
IMPORT CONNECTION PARAMETERS
The connection parameters can be imported from the Logix controller by selecting the
Import
Connection Parameters from Online Controller
option under the
Import
menu of the Class 1