Setup
Page 99 of 178
Figure 3.121
–
IDS Copy
–
Internal Source Type
The destination instance is Not Applicable for the internal data space. The Destination Offset
is the offset in the
Internal Data Space (IDS)
which has a max of 100,000 bytes. The Count is
the number of
bytes
that will be copied.
3.7.2.2.
EIP TARGET
When copying data from the ControlNet interface to the EtherNet/IP Target input assembly,
the destination type needs to be EIP Target.
Figure 3.122
–
IDS Copy
–
EtherNet/IP Target Destination Type
The destination instance will be the connection number, which in this case is always
Connection 0
. The Destination Offset is the offset in the
Mapped Data
section of the
EtherNet/IP input assembly from where the data must be copied. The Count is the number of
bytes
that will be copied. The
Mapped Data
section will be available when using the provided
UDT for the Input Assembly.
Figure 3.123
–
EtherNet/IP Input Mapped Data UDT