Setup
Page 45 of 178
Keying is not enabled and no key information will be sent in the connection
establishment.
Compatible
Keying has been enabled with compatibility enabled. This will allow devices
with older firmware to also establish a connection.
Exact
Keying has been enabled and the exact device with specific firmware revision
will allow the establishment of the connection.
Vendor ID
The Vendor ID of the target device.
Device Type
The Device Type of the target device.
Product Code
The Product Code of the target device.
Major Revision
The Major Revision of the target device.
Minor Revision
The Minor Revision of the target device.
Advanced (Note: Changing these values is not recommended)
Tick Time
For unconnected messages, this is the time for each tick to calculate the
unconnected Time-Out time.
Time-Out Ticks
The number of ticks before the unconnected message is set for timeout.
Time-Out Multiplier
This is the multiplier of the RPI to define the connection timeout time.
Time-Out
The unconnected message timeout time (read-only)
Transport Trigger Direction
The Transport Trigger direction;
Server
or
Client
.
Configuration
Data
The configuration data that is sent with the forward open connection
establishment. The data will need to be entered as a space-delimited,
hexadecimal string. For example: 0A 0D 12 EE
The configuration size will increase by one, each time a byte is added to the
configuration.
Table 3.4
–
Scheduled ControlNet Connection Parameters
B.
IMPORT TOOL
PREPARATION
Before the connection information can be imported some preparation is required using
Studio5000 and a Logix controller:
1.
In Studio5000 create a new project and add the required ControlNet device in the IO
tree. If the device’s profile supports configuration, then configure the device as
required.
2.
Download the project to a Logix controller.