Operation
Page 134 of 178
Ethernet Port1 Status
21
1
SINT
Status of Ethernet Port 1.
Link Up
21.0
-
BIT
0
–
The Link is down
1
–
The Link is up
Ethernet Port2 Status
22
1
SINT
Status of Ethernet Port 2.
Link Up
22.0
-
BIT
0
–
The Link is down
1
–
The Link is up
DLR Status
23
1
SINT
DLR Status when DLR is enabled
Enabled
23.0
-
BIT
0
–
Disabled
1
–
Enabled
Topology
23.1
-
BIT
0
–
Linear
1
–
Ring Topology
Status
23.2
-
BIT
0
–
Normal
1
–
Fault
NTP Status
24
1
SINT
NTP Status when NTP is enabled
Enabled
24.0
-
BIT
0
–
Disabled
1
–
Enabled
Connection to Server
24.1
-
BIT
0
–
Not Locked to a NTP Server
1
–
Locked to a NTP Server
Firmware Major Rev
25
1
SINT
Application Firmware Major Rev
Firmware Minor Rev
26
1
SINT
Application Firmware Minor Rev
Firmware Micro Rev
27
1
SINT
Application Firmware Micro Rev
Module Status
28
2
INT
General Module status
Config Valid
28.0
-
BIT
The configuration in the module is valid
Routing Inhibited
28.1
-
BIT
Routing has been inhibited
EIP Originator Comms Ok
28.2
-
BIT
EtherNet/IP communication is ok when the
module is configured as a EtherNet/IP
Originator.
Modbus Communication Ok
28.3
-
BIT
Modbus communication is ok when the module
is configured as a Modbus Master or Modbus
Slave.
CNet Originator Comms Ok
28.4
-
BIT
ControlNet communication is ok when the
module is configured as a ControlNet
Originator.
EtherNet/IP Owned
28.5
-
BIT
Indication that the module is owned by a
EtherNet/IP originator when the module is
operating as a EtherNet/IP target.
ControlNet Owned
28.6
-
BIT
Indication that the module is owned by a
ControlNet originator when the module is