Setup
Page 82 of 178
Figure 3.94
–
IDS Copy - Modbus Destination Type
The destination instance will be the Modbus register type required.
Figure 3.95
–
IDS Copy - Modbus Destination Instance
The Destination Offset is the Modbus Register offset to where the data must be copied. The
Count is the number of
bytes
that will be copied. See the Internal Data Space Mapping section
for more information regarding the operation.
3.6.5.
E
THER
N
ET
/IP
O
RIGINATOR
The ControlNet Router can operate as a EtherNet/IP connection originator for cyclic (Class 1)
or explicit (Class 3 or UCMM) data exchange. The explicit messaging can be setup in the
EtherNet/IP Devices
and
EtherNet/IP Map
in the Master configuration while the cyclic class 1
connections are added to the
EtherNet/IP Connections
node under the module in the Slate
project tree.
3.6.5.1.
ETHERNET/IP CLASS 1 DEVICE CONNECTIONS
The ControlNet Router can establish up to 10 cyclic Class 1 EtherNet/IP connections to
EtherNet/IP devices. This can be done by either manually entering the connection data into
the Connection Parameter window or by using the Import Tool that will automatically extract
the required connection and configuration parameters from an existing Logix configuration.
A.
MANUAL CONFIGURATION
A class 1 connection can be added to the
EtherNet/IP Connections
tree by right-clicking on the