Setup
Page 32 of 178
The user must enter the ControlNet node number of the ControlNet Router that will be used.
The assembly instance and size must also be added for the input, output, and configuration
in the connection parameters section. Below are the required connection parameters.
NOTE:
The input and output assembly connection sizes will be dynamic and
based on the sizes of the Mapped Data for the input and output (as shown
below).
Figure 3.19
–
Mapped data for input and output
Connection Parameter
Assembly Instance
Size
Input
130
8 + Input Mapped Data Size (8-bit)
For example: if the input mapped data
is 400 then the input assembly size will
be 408.
Output
131
4 + Output Mapped Data Size (8-bit)
For example: if the output mapped
data is 400 then the output assembly
size will be 404.
Configuration
102
0 (8-bit)
Table 3.3
–
ControlNet Logix class 1 connection parameters for the ControlNet Router