Setup
Page 68 of 178
D.
DIAGNOSTIC DATA
Various diagnostic items can be displayed in the FTView using the Diagnostic File. The
diagnostic file number is N11. The description of each diagnostic data point is tabulated
below.
Offset
Group Description
0
General
Sta
tus
ControlNet Router Status
Bit 0
–
Config Valid
Bit 1
–
Routing Inhibited
1
ControlNet Node Number
2
ControlNet LED State
3
ControlNet Net Mode
4
ControlNet Router Internal Temperature
5
Co
n
tr
o
lN
et
S
tat
s
Rx Packet Count
6
Tx Packet Count
7
Scheduled Tx Packet Count
8
Scheduled Rx Packet Count
9
Unscheduled Tx Packet Count
10
Unscheduled Rx Packet Count
11
Routed Class 3 Forward Open
12
Routed Class 3 Forward Close
13
Routed Class 3 Message
14
Routed UCMM Message
15
P
CCC
-
Et
h
erne
t
PCCC Connection Requests
16
PCCC Read Requests
17
PCCC Write Requests
18
PCCC Unsupported Command
19
PCCC Unsupported FNC Code
20
PCCC Client Not Found
21
PCCC Client Max Reached
22
PCCC File Not Found
23
Current Connections
Table 3.8 - Diagnostic File
3.6.2.
E
THER
N
ET
/IP
T
ARGET
A controller (e.g. Logix controller) can own the ControlNet Router over EtherNet/IP using a
Class 1 EtherNet/IP connection when the ControlNet Router is operating as an EtherNet/IP
target. This will allow the ControlNet Router to exchange data with the controller using the
input and output assembly of the Class 1 EtherNet/IP connection. Data from ControlNet
devices can be mapped to the Logix controller over EtherNet/IP.