4. Configuration
64
Figure 4-2. Time Synchronization Configuration
Configuration
Description
Default
Options
Time Zone
Time zone. Difference between UTC(Universal
Time Coordnated) time and the local time
-03:00
-12:59 to +13:59
Enable IRIG-B
Enables the synchronism through the IRIG-B
protocol.
Disabled
Disabled
Enabled
Priority
(IRIG-B)
Sets the priority of the IRIG-B sync source
regarding the other sources.
When enabled, the sync for the IRIG-B
protocol should be the prior source. By this
reason, the field is read-only.
1
1
2
3
Time-Out (s)
In case of IRIG-B signal failure, it defines the
maximum time (seconds) expected for signal
restoration before seeking another source of
timing.
3
3 a100
Priority
(Control Center)
Sets the priority of Control Center sync source
regarding the other sources. The smaller the
value of the field, the higher priority of the sync
source.
2
1
2
3
Enable SNTP
Enables the synchronism through the SNTP
protocol.
Disabled
Disabled
Enabled
Priority
(SNTP)
Sets the priority of SNTP sync source
regarding the other sources. The smaller the
value of the field, the higher priority of the sync
source.
3
1
2
3
Ethernet Interface
Sets the Ethernet port through which is done
the communication with the SNTP server used
for clock synchronization.
NET 1
NET 1
NET 2
NET 3
NET 4
NET 5
NET 6
Period for SNTP
Synchronization (s)
Time interval (seconds) that must be waited
between two synchronization requests
60
1 to 255