4. Configuration
121
DNP3
– Data Types
Table 4-73 shows the type of the variable supported by HX3040 for each one of the DNP3 protocol
data types.
Mapping Type
IEC Variable
Types
StaticGroup Variation
EventGroup Variation
Event Class
Range
BI: Binary
Input
BOOL
BIT
g01v01 - Binary input packed format
g01v02 - Binary input with flags
g02v01
– Binary input event without
time
g02v02 - Binary input event with
absolute time
g02v03 - Binary input event with relative
time
0..3
DBI: Double
Binary Input
DBP
g03v01
– Double-bit binary input
packed format
g03v02
– Double-bit binary input with
flags
g04v01 - Double-bit binary input event
without ime
g04v02
– Double-bit binary input event
with absolute time
g04v03
– Double-bit binary input event
with relative time
0..3
BO: Binary
Output
BOOL
DBP
BIT
g10v01 - Binary output packed
format
g10v02 - Binary output with flags
0
CN: Counter
UINT
g20v02
– Counter 16 bits with flag
g20v06 - Counter 16 bits without flag
g22v02 - Counter event 16 bits with flag
g22v06 - Counter event 16 bits with flag
and time
0..3
UDINT
g20v01 - Counter 32 bit with flag
g20v05 - Counter 32 bit without flag
g22v01 - Counter event 32 bits with flag
g22v05 - Counter event 32 bits with flag
and time
0..3
FCN: Frozen
Counter
UINT
g21v02 - Frozen counter 16 bits with
flag
g21v10 - Frozen 16 bits counter
without flag
g23v02 - Frozen counter event 16 bits
with flag
g23v06 - Frozen counter 16 bits event
with flag and time
0..3
UDINT
g21v01 - Frozen counter 32 bits with
flag
g21v09 - Frozen counter 32 bits
without flag
g23v01 - Frozen counter event 32 bits
with flag
g23v05 - Frozen counter event 32 bits
with flag and time
0..3
AI: Analog
Input
INT
g30v02 - Analog input 16 bits with
flag
g30v04 - Analog input 16 bits without
flag
g32v02
–Analog input event 16 bits
without time
g32v04 - Analog input event 16 bits with
time
0..3
DINT
g30v01 - Analog input 32 bits with
flag
g30v03 - Analog input 32 bits without
flag
g32v01
– Analog input event 32 bits
without time
32v03 - Analog input event 32 bits with
time
0..3
REAL
g30v05 - Analog input single
precision, floating-point with flag
g32v05
– Analog input event single
precision, floating-point without time
g32v07 - Analog input event single
precision, floating-time with time
0..3
AO: Analog
Output
INT
g40v02 - Analog output status 16
bits with quality
0
DINT
g40v01 - Analog output status 32
bits with quality
0
REAL
g40v03 - Analog output status single
precision, floating-point with flag
0
Table 4-73. DNP3 Variable Declaration
DNP3 Ethernet Client
This protocol is available for the Hadron Xtorm Series CPUs on its Ethernet channels. When
selecting this option at MasterTool Xtorm, the CPU becomes a client of the DNP3 communication.
HX3040 CPUs support up to 12 drivers for communication. Therefore, the top limit of instantiating
for DNP3 Client drivers also depends on how many drivers of other protocols are instantiated. This
protocol is only available when the CPU is in execution mode (Run Mode).
Follow the steps below in order to set this protocol: