4. Configuration
149
allowing connection with up to five IEC 60870-5-104 client devices. For each client, the driver has a
unique event queue with the following characteristics
Size: 4.500 events
Overflow policy: keeps the most recent event
Follow the steps below in order to set this protocol:
Add the IEC 60870-5-104 Server protocol instance to one of the available Ethernet channels
(NET 1 to NET 6)
To execute this procedure see, Inserting a Protocol Instance
Set the Ethernet interface. See Ethernet Interfaces Configuration
Set the general parameters of the IEC 60870-5-104 Server protocol with the connection modes
Port or IP (for the later, set TCP port number also)
Add and set the devices, defining the requested parameters
Add and set the IEC 60870-5-104 mappings, specifying the variable name, object type, object
address, size, range, event class, dead band and dead band type
Set the link layer parameters, specifying the addressing, the timeouts communication and the
communication parameters
Set the link layer parameters, configuration of the synchronism , commands, as well as the
transmission mode of
Integrated Totals
objects
The following items describe each one of these settings.
General Parameters
The general configuration of the DNP3 Server (Figure 4-34) follow the parameters shown below
(Table 4-102):
Figure 4-34. IEC 60870-5-104 Server General Parameter Screen
Parameter
Description
Default
Possibilities
Connection Mode
Sets the connection mode with the
Connected Client modules
Port
Port
IP
TCP Port
Defines which RTU TCP port number is
used for communication with the Client
Connected modules, case "IP" is
selected in the "Connection Mode".
2404
1 a 65535
Table 4-102. IEC 60870-5-104 Server General Parameter Configuration
Data Mapping
The configuration of the IEC60870-5-104 Server data relations (Figure 4-35), follow the parameters
shown below (Table 4-103):