4. Configuration
155
Diagnostic Variable T_DIAG_IEC104_SERVER_1.*
Size
Description
wSize
WORD
Queue size
wUsage
WORD
Number of events in the queue
dwReserved_0
DWORD
Reserved
dwReserved_1
DWORD
Reserved
tStats
wRXFrames
WORD
Number of frames received
wTXFrames
WORD
Number of frames sent
wCommErrors
WORD
Communication error counter
including errors in the Physical
Layer, Data Link Layer and
Transport Layer.
dwReserved_0
DWORD
Reserved
dwReserved_1
DWORD
Reserved
Table 4-109. IEC 60870-5-104 Server Diagnostics
Association of the objects with the DNP3 protocol
Table 4-110 provides the allowed associations between IEC 60870-5-104 and DNP3 protocols.
Tipo do Objeto IEC 60870-5-104
Grupo DNP3
Single Point Information (M_SP_NA)
g01
– Digial input
Double Point Information (M_DP_NA)
g03
– Double digital input
Step Position Information (M_ST_NA)
-
Measured Value, normalized value (M_ME_NA)
g30
– Analog input
Measured Value, scaled value (M_ME_NB)
g30 - Analog input
Measured Value, short floating point value (M_ME_NC)
g30 - Analog input
Single Command (C_SC_NA)
g10
– Digital output
Double Command (C_DC_NA)
g10 - Digital output
Regulating Step Command (C_RC_NA)
g10 - Digital output
Setting Point Command, normalized Value (C_SE_NA )
g40
– Analog output
Setting Point Command, scaled Value (C_SE_NB )
g40 - Analog output
Setting Point Command, short floating point Value (C_SE_NC )
g40 - Analog output
Table 4-110. Association of the IEC 60870-5-104 object types with their equivalents in the DNP3
ATTENTION:
Integrated Totals (MIT_NA):
It is not allowed to associate a variable used as frozen accountant
simultaneously in IEC 60870-5-104 and DNP3 procolos.
Commands for Output Points and Counters
The commands received by the DNP3 Server driver may have the following destinations:
Internal Points
Output Module (e.g. HX2320)
Driver DNP3 Client
Interception (CommandReceiver function block)
Internal Points
Internal points are those ones represented by variables which are not associated to any of the others
destinations described above. For this type of point, are not supported pulsed commands. If the IEC
60870-5-104 server receives a pulsed command (single or double) to an internal point, it return a
failure code (negative confirmation), unless it is used the command intercepter.