4. Configuration
72
Internal>IEC 60870-5-104 Counters
Internal Quality
IEC 60870-5-104 Quality
Flags
VALIDITY
FLAG_RESTART
ANY
-
FLAG_COMM_FAIL
ANY
-
FLAG_REMOTE_SUBSTITUTED
ANY
-
FLAG_LOCAL_SUBSTITUTED
ANY
-
FLAG_FILTER
ANY
-
FLAG_OVERFLOW
ANY
OVERFLOW
FLAG_REFERENCE_ERROR
ANY
-
FLAG_INCONSISTENT
ANY
-
FLAG_OUT_OF_RANGE
ANY
-
FLAG_INACCURATE
ANY
-
FLAG_OLD_DATA
ANY
-
FLAG_FAILURE
ANY
INVALID
FLAG_OPERATOR_BLOCKED
ANY
-
FLAG_TEST
ANY
-
ANY
VALIDITY_INVALID
INVALID
Tabela 4-12. Internal Conversion to IEC 60870-5-104 to Counters
IEC 61850 Conversion
Table 4-13 relates the quality type of internal points to the IEC 61850 quality for Hadron Xtorm
Series available for HD8500.
Internal-> IEC 61850
Internal Quality Flags
VALIDITY IEC 61850
IEC 61850 Flags
FLAG_RESTART
VALIDITY_QUESTIONABLE
OLDDATA
FLAG_COMM_FAIL
VALIDITY_QUESTIONABLE
OLDDATA
FLAG_REMOTE_SUBSTITUTED
GOOD
Source = SUBSTITUTED
FLAG_LOCAL_SUBSTITUTED
GOOD
Source = SUBSTITUTED
FLAG_FILTER
VALIDITY_QUESTIONABLE OR
VALIDITY_INVALID
OSCILLATORY
FLAG_OVERFLOW
VALIDITY_INVALID
OVERFLOW
FLAG_REFERENCE_ERROR
VALIDITY_QUESTIONABLE OR
VALIDITY_INVALID
BADREFERENCE
FLAG_INCONSISTENT
VALIDITY_QUESTIONABLE
INCONSISTENT
FLAG_OUT_OF_RANGE
VALIDITY_QUESTIONABLE OR
VALIDITY_INVALID
OUTOFRANGE
FLAG_INACCURATE
VALIDITY_QUESTIONABLE
INNACURATE
FLAG_OLD_DATA
VALIDITY_QUESTIONABLE
OLDDATA
FLAG_FAILURE
VALIDITY_INVALID
FAILURE
FLAG_OPERATOR_BLOCKED
GOOD
OPERATORBLOCKED
FLAG_TEST
GOOD
TEST
Table 4-13. Internal to IEC 61850 Conversion
The conversion process of internal quality format to IEC 61850 follows the recommendations
defined by IEC 61850 standard. According to this standard, the validity field is set according to the
quality flags. Some flags allow the validity to take both VALIDITY_QUESTIONABLE as
VALIDITY_INVALID. In these cases, the assumed validity is defined at the point to be converted.
MODBUS Internal Quality
As the MODBUS standard does not specify types of quality for each point, the Hadron Xtorm Series
allows the mapping of quality variables for each MODBUS point through its own internal structure.