4. Configuration
130
Configurations
Description
Default
Possibilities
Polling (ms)
Sets the period (ms) that
the request occurs.
1000
0 to 86400000
Diagnostic Variable
Name of the symbolic
variable that will receive
the diagnosis of request.
-
Name of a variable declared in a program or
GVL
Table 4-79. Configuration of DNP3 Client Custom Requests
Notes:
Generate Diagnostic Variables:
The diagnostic symbolic variables can be generated automatically
through the "Generate Diagnostics Variables" button. A click on it creates a
T_DIAG_DNP_CLIENT_REQUEST_1", variable for each one of the requests, on the
"ReqDiagnostics" GVL.
Qualifier:
Identifies the request type. The available options depend on the type of the Object
Variation. Table 4-80 describes the types of Qualifier; Table 4-81 indicates their possible values for
each one of the request groups.
Function Type
Configurations
Description
Qualifier
All
All points of the group and variation are required
Range
Only will be requested a range of points defined
by the columns "Start" and “Stop”
Counter
To request a defined number of events in the
"Counter" column, for example, "read 10
events."
Table 4-80. Qualifier Types in DNP3 Client Parameters
Object Variation
Allowed Qualifier
g01v00 - Binary input default variation.
g01v01 - Binary input packed format.
g01v02 - Binar input with flags.
All
Range
g02v00 - Binary input event default variation.
g02v01
– Binary input event without time.
g02v02 - Binary input event with absolute time.
g02v03 - Binary input event with relative time.
All
Counter
g03v00 - Double-bit binary input default variation.
g03v01
– Double-bit binary input packed format.
g03v02 - Dobule-bit binary input with flags.
All
Range
g04v00
– Double-bit binary input event default variation.
g04v01
– Double-bit binary input event without time.
g04v02
– Double-bit binary input event with absolute time.
g04v03
– Double-bit binary input event with relative time.
All
Counter
g10v00 - Binary output default variation.
g10v01 - Binary output packed format.
g10v02 - Binary output with flags.
All
Range
g20v00 - Counter default variation.
g20v01 - Counter 32 bits with flag.
g20v02 - Counter 16 bits with flag.
g20v05 - Counter 32 bits without flag.
g20v06 - Counter 16 bits without flag.
All
Range
g21v00 - Frozen counter default variation.
g21v01 - Frozen counter 32 bits with flag.
g21v02 - Frozen counter 16 bits with flag.
g21v09 - Frozen counter 32 bits without flag.
g21v10 - Frozen counter 16 bits without flag.
All
Range