4. Configuration
110
Device Configuration
The client devices configuration, depicted on Table 4-61, follows the parameters:
Figure 4-19. Device General Parameters Settings
Configuration
Description
Default
Options
IP Address
Server IP address
0.0.0.0
1.0.0.1 to
223.255.255.254
TCP Port
TCP Port
502
2 to 65534
Slave Address
MODBUS Slave address
1
0 to 255
Table 4-61. MODBUS RTU Client General Configurations
Notes:
IP Address:
IP address of Modbus Server Device.
TCP Port:
If there are multiple instances of the protocol added in a single Ethernet interface,
different TCP ports must be selected for each instance. Some TCP ports are reserved. See Reserved
TCP Ports.
Slave address:
According to the MODBUS standard, the valid address range for slaves is 0 to 247,
where addresses 248 to 255 are reserved. When the master sends a command of writing with the
address set to zero, it is performing broadcast requests on the network.
Communication Time-out
The communication time-out parameters of the MODBUS Client protocol, found on the button
“Advanced...” of the configuration screen, are divided into: maximum number of concurrent
requests, communication time-out, time-out connection mode and downtime.
Configuration
Description
Default
Options
Maximum Number
of Simultaneous
Requests
Number of simultaneous
request the client can ask to
the server
1
1 to 8
Communication
Time-out
Application level time-out in
ms
3000
10 to 65535
Mode
Defines when the connection
with the server is finished by
the client
Connection is closed
after an inactive time
of (s):10 to 3600
- Connection is closed after a time-
out.
- Connection is closed at the end of
each communication
- Connection is closed after an
inactive time of (s): 10 to 3600.
Inactivity Time
Inactivity time
10
3600
Table 4-62. MODBUS Client Advanced Settings