4. Configuration
150
Parameter
Description
Default
Possibilities
Value Variable
Symbolic variable name
-
Variable name declared in a program or GVL
Object Type
Configruation of the IEC 60870-
5-104 object type
-
Single Point Information
Double Point Information
Step Position Information
Measured Value (Normalized)
Measured Value (Scaled)
Measured Value (Short Floating Point)
Integrated Totals
Single Command
Double Command
Regulating Step Command
Setting Point Command (Normalized)
Setting Point Command (Scaled)
Setting Point Command (Short Floating Point)
Object Address
Index of the first IEC 60870-5-
104 mapping point
-
1 a 65535
Size
Define the maximum amount of
data that a IEC 60870-5-104
mapping can access.
-
1 a 86400000
Range
Address range of the data set
-
-
Counter
Variable
Symbolic variable name that will
contain the data of the counter
variable.
-
Variable name declared in a program, GVL or
counter module
Dead Band
Variable
Name of the symbolic variable
that will contain the data of the
dead band.
-
Variable name declared in a program or GVL
Dead Band
Type
Define the Dead Band type to
be used in the mapping
Disabled
Absolute
Disabled
Integrated
Select Required
Define whether for the
execution of a command is
required a prior select, or not.
False
True
False
Short Pulse
Set the short pulse time of the
IEC 60870-5-104 digital
command.
1000
1 a 86400000
Long Pulse
Set the long pulse time of the
IEC 60870-5-104 digital
command.
2000
1 a 86400000
Table 4-103. IEC 60870-5-104 Server Mapping Configuration
Notes:
Value Variable:
Name of the symbolic variable to be mapped. When a reading command is sent, the
return sent in response is stored in this variable. In case of a writing command, the written value is
also stored in this variable. The variable may be simple, array or array element and may be in
structures.
Counter Variable:
This field applies only in the mapping of objects of type
Integrated Totals
, his
being the counter variable to be manipulated in the process. It should have the same size and type of
the variable mapped in the
Variable Value
column, which shall be read by the client or reported to
the customer in case of events.
ATTENTION:
When the
Counter Variable
is associated with a quality variable, so that this quality is transferred
to the frozen variable in the
freeze
command, to be associated with a quality variable to frozen
variable. This can be done through the tab
Internal Points.
Dead Band Variable:
This field applys only to analog input variable mappings (Measured Value
object types). It must have the same type and size of the variable mapped on Value Variable column.