4. Configuration
153
Parameter
Description
Default
Possibilities
Enable Time
Synchronization
Option to Enable/Disable time
synchronization request.
Disabled
Disabled
Enabled
Maximum Time
Between Select and
Operate (s)
Period in which the selection
command remains active (starts
counting from the confirmation of
receipt of the selection command)
waiting for the Operate command.
5
1 a 180
Maximum Time to
Complete a Command
Execution (s)
Maximum time to treat a command
when transferred to a DNP3 Client or
even an output card before it is
answered failure by timeout.
2
1 a 180
Transmission Mode of
Analog Inputs Events
Transmission Mode of Analog Inputs
Events.
All Events (SOE)
All Events (SOE)
Most Recent Events
Transmission Mode
Transmission mode of counters data.
Freeze by counter-
interrogation
command, transmit
spontaneously
Freeze by counter-
interrogation command,
transmit spontaneously
Freeze and transmit by
counter-interrogation
command
Table 4-106. IEC 60870-5-104 Server Application Layer Configuration
Notes:
Enable Time Synchronization:
If this option is checked, the IEC 60870-5-104 Server will adjust the
clock of the CPU when receiving a synchronization command.
ATTENTION:
When the time synchronization option is selected in more than one server (parameter “Enable Time
Synchronization”), the times received at different servers will be overwritten on the system clock in
a short space of time. This may cause an undesirable behavior, due to time delays in the messages
propagation and system load.
Maximum Time to Complete a Command Execution:
This parameter does not apply when the
command is intercepted by the command interception function block (CommandReceiver). In this
case the maximum time to process the command is defined by a function block parameter.
Transmission Mode of Analog Input Events:
The transmission modes of the analog inputs events
are as follows:
Function Type
Configurations
Description
Transmission Mode
of Analog Inputs
Events
All Events(SOE)
All analog events generated are sent.
Most Recent Events
Sent only the latest in each analog point.
Table 4-107. Transmission Modes of Analog Input Events in IEC 60870-5-104 Server
Transmission Mode:
Available transmission modes of the frozen counters(integrated totals) are the
following: